What article covers requirements for outside branch circuits and feeders run on or between buildings?

This article covers feeders and branch circuits located outside on premises between buildings or poles, or for equipment on the outside of buildings or poles.

Table 225.2 refers to other articles in the Code which are pertinent to outside branch circuits and feeders.

Table 225.2. Other Articles

 

Article

Branch Circuits

210

Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power-Limited Circuits

725

Communications Circuits

800

Community Antenna Television and Radio Distribution Systems

820

Conductors for General Wiring

310

Electrically Driven or Controlled Irrigation Machines

675

Electric Signs and Outline Lighting

600

Feeders

215

Fire Alarm Systems

760

Fixed Outdoor Electric De-icing and Snow-Melting Equipment

426

Floating Buildings

553

Grounding

250

Hazardous (Classified) Locations

500

Hazardous (Classified) Locations, Specific

510

Marinas and Boatyards

555

Messenger Supported Wiring

396

Mobile Homes, Manufactured Homes, and Mobile Home Parks

550

Open Wiring on Insulators

398

Over 600 Volts, General

490

Overcurrent Protection

240

Radio and Television Equipment

810

Services

230

Solar Photovoltaic Systems

690

Swimming Pools, Fountains, and Similar Installations

680

Use and Identification of Grounded Conductors

200

I. General

225.3

Calculation of Loads 600 Volts, Nominal, or Less

Use 210.10 for outdoor branch circuits and Part III of Article 220 for outdoor feeders.

Conductors must be insulated or covered within 3 m (10 ft.) of a building. Conductors in raceways or cables except MI must have thermoplastic or rubber insulation. An exception is made for equipment grounding conductors and grounded circuit conductors. Section 310.8 governs wet locations.

225.5

Size of Conductors 600 Volts, Nominal, or Less

Size in accordance with Section 310.15. Determine loads in accordance with Section 220.10 and Part III of Article 220.

225.6

Conductor Size and Support

(A) Overhead Spans

600 V or less, up to 15 m (50 ft.): 10 AWG copper, 8 AWG aluminum except where supported by a messenger wire

600 V or less, over 15 m (50 ft.): 8 AWG copper, 6 AWG aluminum except where supported by a messenger wire

More than 600 V: 6 AWG copper, 4 AWG aluminum for open conductors; 8 AWG copper, 6 AWG aluminum for cable

(B) Festoon Lighting

Use 12 AWG or Larger for festoon lighting except where messenger wires support them, over 12 m (40-ft.) span require messenger wire support.

225.7

Lighting Equipment Installed Outdoors

225.10

Wiring on Buildings

225.11

Circuit Exits and Entrances

Refer to Sections 230.52, and 230.54.

225.12

Open Conductor Supports

225.14

Open Conductor Spacings

225.15

Supports Over Buildings

Refer to Section 230.29.

225.16

Attachment to Buildings

Refer to Sections 230.26 and 230.27.

225.17

Masts as Supports

225.18

Clearance from Ground

Open conductors and open multiconductor cables not over 600 V must conform to the following:

3 m (10 ft.): above finished grade: 150 V to ground

3.7 m (12 ft.): over residential driveways and commercial areas not subject to truck traffic: 300 V to ground limitation

4.5 m (15 ft.): same as 3.7 m (12 ft.) above: exceeding 300 V to ground

5.5 m (18 ft.): above streets, driveways, etc. subject to truck traffic as well as land used by vehicles such as forest, grazing, etc.

225.19

Clearances from Buildings for Conductors of Not over 600 Volts, Nominal

(A) Above Roofs. Not less than 2.5 m (8 ft.) vertical clearance from the roof surface maintained for a distance of not less than 900 mm (3 ft.) in all directions from the edge of the roof except the final span to the attachment to the building. If subject to pedestrian or vehicular traffic, vertical clearances should be in accordance with Section 225.18. Other exceptions are as follows:

900 mm (3 ft.) clearance: voltage between conductors not more than 300 V and roof slope is maximum of 100 mm (4 in.) in 300 mm (12 in.).

450 mm (18 in) clearance above the overhanging portion of the roof: voltage between conductors not more than 300 V, not more than 1.8 m (6 ft.) of conductor, 1.2 m (4 ft.) horizontally, do not pass over an overhang and are terminated in approved support or raceway through the roof.

900 mm (3 ft.) clearance does not apply to the final conductor span attached to the roof.

(B) From Nonbuilding or Nonbridge Structures. Clearances in all directions to be a minimum of 900 mm (3 ft.).

(C) Horizontal Clearances. Not less than 900 mm (3 ft.).

(D) Final Spans. Those may be attached to a building but must clear operable windows, fire escapes, and the like by at least 900 mm (3 ft.). If above the top level of a window then it can be reduced to less than 900 mm (3 ft.). There is additional information concerning openings in commercial buildings and vertical clearances.

(E) Zone for Fire Ladders. Allow for fire laddersat least a 1.8 m (6-ft.)-wide space.

225.20

Mechanical Protection of Conductors

Refer to Section 230.50.

225.21

Multiconductor Cables on Exterior Surfaces of Buildings

Refer to Section 230.51.

225.22

Raceways on Exterior Surfaces of Buildings, or Other Structures

They must drain and be raintight in wet locations other than flexible metal conduit as permitted in 348.12(1).

225.24

Outdoor Lampholders

225.25

Location of Outdoor Lampholders

225.26

Vegetation as Support

Not permitted.

II. More Than One Building or Other Source

225.30

Number of Supplies

Where you have more than one building under one management and on the same property you can only have one feeder or branch circuit from the service disconnect supplying each of the additional buildings. The exceptions are noted in (A) through (E).

(A) Special Conditions. You can have additional feeders or branch circuits for fire pumps, emergency systems, legally required standby systems, parallel power production systems, optional standby systems, and systems connected to multiple sources of supply for greater reliability.

(B) Special Occupancies. In a single building where the load is too large for one feeder or branch circuit or in multi-occupancy buildings where there is no space for supplies accessible to all occupants then with special permission you can have additional feeders or branch circuits.

(C) Capacity Requirements. If the load requirements are more than 2000 A and the voltage is not more than 600 V, more than one supply is allowed.

(D) Different Characteristics. More than one supply is allowed if different characteristics, i.e., voltage, frequency, etc. are required.

(E) Documented Switch Procedures. You can have more than one supply if they are under one management and there are documented safe disconnecting procedures.

225.31

Disconnecting Means

Must be provided.

It must be located at the poiint where the wire passes through the building either inside or outside. It must be readily accessible. You are allowed to use the requirements of Section 230.6. There are four exceptions.

225.33

Maximum Number of Disconnects

The provision for disconnecting each supply in 225.30 can consist of no more than six switches or six circuit breakers. Single-pole units can be used on multiwire circuits, one pole for each ungrounded conductor. They must be tied together as a multipole disconnect and will then be counted as one disconnect. An exception is made for the control circuit of a ground-fault protection system or the control circuit of the power operated supply disconnecting means.

225.34

Grouping of Disconnects

All disconnects are to be grouped together. An exception is made for fire pumps. The disconnects for fire pumps, emergency legally required standby or optional standby systems must be located away from the normal supply.

225.35

Access to Occupants

Must be accessible to the occupants except where there is a single management with continuous supervision.

225.36

Suitable for Service Equipment

225.37

Identification

225.38

Disconnect Construction

225.39

Rating of Disconnect

In general, the feeder or branch circuit disconnect must be sized to carry the calculated load as determined in accordance with Article 220. There are special cases where a minimum size is required. They are:

15 A: a single branch-circuit load.

30 A: up to two, two-wire branch circuits

100 A: three-wire: one-family dwelling with six or more two-wire branch circuits or calculated load is 10 kW or more.

60 A: all others.

225.40

Access to Overcurrent Protective Devices

III. Over 600 Volts

225.50

Sizing of Conductors

225.51

Isolating Switches

225.52

Locations

225.53

Type

225.60

Clearances over Roadways, Walkways, Rail, Water, and Open Land

225.61

Clearances over Buildings and Other Structures

Page 2

This article describes requirements for service conductors and equipment for control and protection of services. Figure 230.1 describes where in Article 230 different parts of the service are described.

I. General

A building normally can have only one service. If more than one is permitted as a result of the exceptions provided, then a directory of all services must be placed at each service. For the purposes of Section 230.40, Exception 2, underground conductors sized at least 1/0 are considered one service if they are connected at the supply but not at the load. More than one service is permitted as follows:

(A) Special Conditions

(1) Fire pumps if required.

(2) Emergency systems.

(3) Legally required standby systems.

(4) Optional standby systems.

(5) Parallel power production systems.

(6) Systems designed to connect to multiple sources of supply for enhanced reliability.

(B) Special Occupancies

(1) In multiple-occupancy buildings where there is no room for each tenant to have access to the service equipment, with permission, more than one set of service conductors can be tapped from one service drop or service lateral.

(2) If a single building is too large then with special permission, more than one service may be installed.

(C) Capacity Requirements

(1) If the capacity requirements are larger than 2000 amperes at 600 volts or less.

(2) If a single-phase installation were larger than the utility would normally serve through one service.

(3) With special permission.

(D) Different Characteristics

More than one service is permitted if there are different rate schedules, voltages, phases, frequencies or uses.

(E) Identification

If a building is supplied by more than one service, feeder, or set of branch circuits, a permanent directory or plaque has to be installed at the disconnect location.

230.3

One Building or Other Structure Not to Be Supplied through Another

Service conductors cannot pass through another building.

230.6

Conductors Considered Outside of Building

If conductors have a cover of at least 50 mm (2 in.) of concrete under a building or are installed in a raceway encased in at least 50 mm (2 in.) of concrete or are installed in a vault as per Article 450 Part III, or installed in concrete and under at least 450 mm (18 inches) of earth under a building they are treated as being outside the building.

230.7

Other Conductors in Raceway or Cable

230.8

Raceway Seal

230.9

Clearance from Building Openings

If installed as open conductors or multiconductor cable without an outer jacket, clearance of at least 900 mm (3 ft.) is required from operable windows, doors, porches, fire escapes, stairs, ladders, balconies, and the like. There is an exception for conductors above the top level of a window. Overhead service conductors are not permitted underneath openings through which materials can be moved or obstructing these openings. Vertical clearances under certain conditions are to be maintained in accordance with Section 230.24(B).

230.10

Vegetation as Support Not Permitted

II. Overhead ServiceDrop Conductors

230.22

Insulation or Covering

Insulation or covering is required on individual conductors.

Conductors should have the capacity required for the load in accordance with Article 220 and have enough mechanical strength. The minimum size should be 8 AWG copper or 6 AWG aluminum or copper-clad aluminum. Grounded conductors shall be as required in Section 250.24(B). There is an exception.

Service-drop conductors must not be accessible and comply with the following:

(A) 2.5 m (8 ft.) vertical clearance maintained above the roof with 900 mm (3 ft.) from the edge of the roof is generally the clearance required above roofs with a nominal voltage of 600 V except where the service drop is attached to the side of the building. This is reduced to 900 mm (3 ft.) with a voltage of 300 V and a roof slope of 100 mm (4 in.) in 300 mm (12 in.) or more. It is also reduced to 450 mm (18 in.) above the overhanging portion with a nominal voltage of 300 V if only up to 1.8 m (6 ft.) of service drop conductors, 1.2 m (4 ft.) horizontally, pass over the roof and the conductors end on a support or raceway. Where there is traffic above a roof surface use requirements of Section 230.24(B).

(B) The clearances above the ground vary for conductors with a nominal voltage of 600 V. They are:

3.0 m (10 ft.): voltage of 150 V to ground, service entrance to buildings accessible to pedestrians.

3.7 m (12 ft.): over residential property and no truck traffic commercial areas with voltage to ground not in excess of 300.

4.5 m (15 ft.): at areas listed in 3.7 m (12 ft.) classification when the voltage exceeds 300 V to ground.

5.5 m (18 ft.): over public streets. Private property is included if traveled with commercial vehicles.

(C) Refer to Section 230.9 for clearances from building openings.

(D) Refer to Section 680.8 for clearances from swimming pools.

230.26

Point of Attachment

A minimum clearance of 3.0 m (10 ft.) is required. Compliance with 230.9 and 230.24 is required.

230.27

Means of Attachment

230.28

Service Masts as Support

230.29

Supports over Buildings

III. Underground ServiceLateral Conductors

Generally, they are insulated with the voltage determining the insulation. There are some exceptions for grounded conductors of bare wire and aluminum or copper-clad aluminum cable assemblies.

The conductors must be large enough to carry the load in accordance with Article 220. No smaller than 8 AWG for copper and 6 AWG for aluminum or copper-clad aluminum. An exception is made where the service supplies only a single load on a single branch circuit. The grounded conductor must not be sized less than required in Section 250.24(B).

230.32

Protection against Damage

230.33

Spliced Conductors

IV. Service-Entrance Conductors

230.40

Number of Service-Entrance Conductor Sets

Generally, a service drop or lateral can only supply one set of service conductors. However, one set of service conductors can supply each occupancy or a group of occupancies in a multiple- occupancy building. A second exception for separate enclosures is noted. A third exception is noted for single family or a separate structure. There are two additional exceptions.

230.41

Insulation of Service-Entrance Conductors

Generally, if the conductors are on or enter a building, they should be insulated. Exceptions are made for grounded conductors of bare copper wire and aluminum, copper-clad aluminum cable assemblies in special cases, copper for direct burial where the copper is all right for the soil, and aluminum or copper-clad aluminum part of an assembly rated for direct burial.

230.42

Minimum Size and Rating

(A) General. The ampacity of the conductors is to be either the sum of the noncontinuous load and 125% of the continuous load or the sum of the noncontinuous and continuous loads if the overcurrent devices are rated for operation at 100% of their rating. The loads are calculated in accordance with Article 220. The ratings are determined in accordance with Section 310.15. For busways use the listing or rating of the busway.

(B) Ungrounded Conductors. Use at least the rating of the disconnecting means as specified in Section 230.79(A) through (D).

(C) Grounded Conductors. Size in accordance with Section 250.24(B).

230.43

Wiring Methods for 600 Volts, Nominal, or Less

Only the following methods are permitted: Open wiring on insulators; type IGS cable; rigid metal conduit; intermediate metal conduit; EMT; ENT; service entrance cables; wireways; busways; auxiliary gutters; rigid NMC; cablebus; MC cable; mineral-insulated, metal-sheathed cable; flexible metal conduit or liquidtight flexible metal conduit with certain restrictions; or liquidtight flexible nonmetallic conduit.

To support cables, a cable tray system may be used.

230.46

Spliced Conductors

230.49

Protection against DamageUnderground

230.50

Protection of Open Conductors and Cables against DamageAbove Ground

230.51

Mounting Supports

230.52

Individual Conductors Entering Buildings or Other Structures

230.53

Raceways to Drain

230.54

Overhead Service Locations

Connections to the service drop conductors have to be made raintight with a raintight head or with a gooseneck. The heads or goosenecks must be above the point where the conductors are attached to the building and must be securely attached. Drip loops must be constructed to prevent entrance of moisture. There are other requirements.

230.56

Service Conductor with the Higher Voltage to Ground

V. Service EquipmentGeneral

230.62

Service EquipmentEnclosed or Guarded

Energized parts must be enclosed so that no one can make accidental contact or guarded. If energized parts are not enclosed then they must be guarded as noted in 110.18 and 110.27. If the energized parts are guarded in accordance with 110.27(A)(1), then there has to be a provision for locking or sealing the doors.

Service equipment must be marked for use as service equipment.

VI. Service EquipmentDisconnecting Means

There must be a way to disconnect all conductors in the building from the service-entrance conductors. The disconnect must be readily accessible either outside the building or inside the building nearest the point of entrance of the service conductors. It must have proper markings and be suitable for its use. Service disconnects cannot be installed in bathrooms. If a remote control device is used to actuate the service disconnect then the service disconnect must still be at a readily accessible location. The service disconnecting means must be suitable for the conditions where it is installed. Refer to Articles 500 through 517 for hazardous locations.

230.71

Maximum Number of Disconnects

The provision for disconnecting each service (Section 230.2) or the service entrance conductors (Section 230.40, Exception Nos. 1, 3, 4, or 5) can consist of no more than six switches or six circuit breakers or combinations. Single-pole units can be used for multiwire circuits, one pole for each ungrounded conductor. They must be tied together as a multipole disconnect and will then be counted as one disconnect. An exception is made for the control circuit of a ground-fault protection system, power monitoring equipment, transient voltage surge suppression, or power-operable service disconnecting means.

230.72

Grouping of Disconnects

All disconnects are to be grouped together. There is an exception for a disconnect used for a water pump for fire protection. If there are additional services as permitted in 230.2 for emergency systems, legally required standby or operational standby systems, or fire pumps, then the disconnecting means must be installed away from the normal service disconnecting means so that the possibility of interrupting the services at the same time is reduced. Where multiple occupancies are present, each occupant must have access to his or her own disconnect. There is an exception to this latter requirement for certain management conditions.

230.74

Simultaneous Openings of Poles

230.75

Disconnection of Grounded Conductor

230.76

Manually or Power Operable

230.77

Indicating

230.79

Rating of Disconnect

In general, the service disconnect must be sized to carry the calculated load. There are special cases where a minimum size is required. They are:

15 A: a single branch-circuit load

30 A: up to two, two-wire branch circuits

100 A: three-wire: one-family dwelling

60 A: all other cases

230.80

Combined Ratings of Disconnects

If more than one service switch is used, their combined rating must be at least the rating shown in Section 230.79.

230.81

Connection to Terminals

230.82

Equipment Connected to the Supply Side of Service Disconnect

Among the pieces of equipment allowed to be connected to the supply side of a service switch are: current-limiting devices, meters, instrument transformers, surge protective devices, fire and sprinkler alarms, fire pump equipment, and interconnected electric production sources. Some of these items require separate protection and disconnects. Refer to the NEC® for a complete description and list.

VII. Service EquipmentOvercurrent Protection

(A) Every ungrounded conductor must have an overcurrent device. It must normally not be set higher than the rating of the conductors. There are five exceptions to this and they include: motor starting current; fuses and circuit breakers conforming to Section 240.3(B) or (C) and Section 240.6; six fuses or circuit breakers is the limit for consideration as a service overcurrent device; fire pumps under certain conditions; when permitted by Section 310.15(B)(6) for 120/240 volt, three-wire, single-phase dwelling services.

(B) No overcurrent device is to be placed in a grounded conductor.

The service overcurrent device must be part of the service disconnect or be next to it.

230.92

Locked Service Overcurrent Devices

230.93

Protection of Specific Circuits

230.94

Relative Location of Overcurrent Devices and Other Service Equipment

Some of the items allowed ahead of the overcurrent device are: service switch, surge protectors, protective signaling systems, fire pump, meters, and power-operable service equipment controls.

230.95

Ground-Fault Protection of Equipment

This is required for all services that are 150 V to ground up to 600 V phase to phase, solidly grounded wye, with service switches 1000 A or more. The grounded conductor must be connected directly to ground. No impedance device is allowed. The rest of this section contains information about the setting of these devices, the use of switches and fuses, and performance testing. An exception is allowed for continuous industrial processes where a nonorderly shutdown would be hazardous and for fire pumps. Refer to 517.17(A) for hospitals or other buildings with critical areas or life support equipment.

VIII. Services Exceeding 600 Volts, Nominal

230.200

General

230.202

Service-Entrance Conductors

230.204

Isolating Switches

230.205

Disconnecting Means

230.206

Overcurrent Devices as Disconnecting Means

230.208

Protection Requirements

230.209

Surge Arresters (Lightning Arresters)

230.210

Service EquipmentGeneral Provisions

230.211

Metal-Enclosed Switchgear

230.212

Services over 35,000 Volts

Page 3

I. General

Parts I through VII give requirements for circuits of up to 600 V. Part VIII covers supervised industrial installations up to 600 V. Part IX covers over 600 V.

240.2

Definitions

240.3

Other Articles

Table 240.3 refers to other articles in the Code which pertain to overcurrent profection for specific equipment and systems.

Table 240.3. Other Articles

 

Article

Air-Conditioning and Refrigerating Equipment

440

Appliances

422

Audio Signal Processing Amplification, and Reproduction Equipment

640

Branch Circuits

210

Busways

368

Capacitors

460

Class 1, Class 2, and Class 3 Remote-Control,

725

Signaling, and Power-Limited Circuits Closed-Loop and Programmed Power Distribution System

780

Cranes and Hoists

610

Electric Signs and Outline Lighting

600

Electric Welders

630

Electrolytic Cells

668

Elevators, Dumbwaiters, Escalators, Moving Walks, Wheel Chair Lifts, and Stairway Chair Lifts

620

Emergency Systems

700

Fire Alarm Signaling Systems

760

Fire Pumps

695

Fixed Electric Heating Equipment for Pipelines and Vessels

427

Fixed Electric Space Heating Equipment

424

Fixed Outdoor Electric De-icing and Snow-Melting Equipment

426

Generators

445

Health Care Facilities

517

Induction and Dielectric Heating Equipment

665

Industrial Machinery

670

Luminaires (lighting fixtures), Lampholders, and Lamps

410

Motion Picture and Television Studios and Similar Locations

530

Motors, Motor Circuits, and Controllers

430

Phase Converters

455

Pipe Organs

650

Places of Assembly

518

Services

230

Solar Photovoltaic Systems

690

Switchboards and Panelboards

408

Theaters, Audience Areas of Motion Picture and Television Studios, and Similar Locations

520

Transformers and Transformer Vaults

450

X-Ray Equipment

660

240.4

Protection of Conductors

For other than flexible cords and fixture wires, use ampacities specified in Section 310.15 when calculating overcurrent protection. There are a number of cases where this rule does not necessarily hold true with special requirements. Some of them are: power loss hazard; devices rated 800 amperes or less; devices rated over 800 amperes; tap conductors; motor-operated appliance circuit conductors; motor and motor control circuit conductors; phase converter supply conductors; air conditioning and refrigeration equipment circuit conductors; transformer secondary conductors; capacitor circuit conductors; electric welder circuit conductors; remote control signalling and power limited circuit conductors; and fire protective alarm system circuit conductors. Refer to the NEC® for a complete list and for other sections and articles that may be relevant.

240.5

Protection of Flexible Cords, Flexible Cables, and Fixture Wires

240.6

Standard Ampere Ratings

The standard ratings for fuses and inverse time circuit breakers are: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, and 6000 A. Fuses are also rated at 1, 3, 6, 10, and 601 A. There is a requirement for circuit breakers having external adjustable means and for restricted access adjustable trip circuit breakers.

240.8

Fuses or Circuit Breakers in Parallel

240.9

Thermal Devices

240.10

Supplementary Overcurrent Protection

240.12

Electrical System Coordination

If an orderly shutdown is required to reduce hazards to equipment and personnel, the following method can be used; coordinated short-circuit protection and/or overload indication.

240.13

Ground-Fault Protection of Equipment

For solidly grounded wye systems that are more than 150 V to ground and not exceeding 600 V phase to phase, ground-fault protection of equipment must be provided for each main disconnecting means rated 1000 A or more, in accordance with Section 230.95. The three exceptions are where an orderly shutdown in an industrial process is required, for fire pumps, and if the disconnect is protected by service ground-fault protection.

II. Location

240.20

Ungrounded Conductors

An overcurrent device (fuse or circuit breaker) has to be connected in series with each ungrounded conductor. An overcurrent relay with a current transformer is allowed. Generally, a circuit breaker has to open all ungrounded conductors. Single-pole circuit breakers are permitted under certain conditions listed in this section. In a closed-loop power distribution system, listed devices can be used instead of fuses or circuit breakers.

240.21

Location in Circuit

This section lists the location of the overcurrent device in relation to the ungrounded circuit conductor.

(A) Branch-Circuit Conductors. If a branch-circuit tap meets the requirements of Section 210.19, then the overcurrent protection can be located in accordance with that Section.

(B) Feeder Taps. Taps can be made at conductors without overcurrent protection at the tap as noted in section 240.21(B)(1) through (5) below. The provisions of 240.4(B) cannot be applied for tap conductors.

(1) Taps Not over 3 m (10 Feet) Long. They may be tapped to a feeder or transformer secondary without overcurrent protection when the tap is not longer than 3 m (10 ft.); the rating of the tap conductor is not less than the loads and devices it supplies and the overcurrent device at the end of the tap; the tap ends at the device it supplies; the tap conductors are enclosed in a raceway, and for field installations where the tap leaves the enclosure of the tap the rating of the overcurrent device on the line side of the tap is not more than 10 times the ampacity of the conductors.

(2) Taps Not over 7.5 m (25 Feet) Long. When the tap is not longer than 7.5 m (25 ft.) it does not require protection if the ampacity of the tap is at least one-third the rating of the feeder or overcurrent protection it was tapped from; ends in a single overcurrent device rated for the device; and is protected from physical damage by an approved method.

(3) Taps Supplying a Transformer [Primary Plus Secondary Not over 7.5 m (25 Feet) Long]. The rule is similar to the 7.5 m (25 ft.) tap (item c above). No overcurrent protection is required for a tap for a feeder supplying a transformer if the ampacity of the primary wires is at least one-third the rating of the overcurrent device protecting the feeder; when you multiply the rating of the conductors supplying the secondary by the ratio of the secondary to primary voltage it should be at least one-third the feeder protective overcurrent device rating; if both primary and secondary wires are not longer than 7.5 m (25 ft.) combined; the primary and secondary conductors are protected in an approved way from physical damage; and the secondary conductors end in a single overcurrent device limiting the load current to that permitted by Section 310.15.

(4) Taps over 7.5 m (25 Feet) Long. No overcurrent protection is required for a tap located in manufacturing installations with bays over 11 m (35 ft.) in height if the horizontal length is not longer than 7.5 m (25 ft.) with the overall length not longer than 30 m (100 ft.). All the rules of the tap not over 7.5 m (25 ft.) tap rule (2 above) apply, and in addition, the tap conductors must be at least 6 AWG copper or 4 AWG aluminum; they can not go through floors, walls, or ceilings; the tap must be least 9 m (30 ft.) from the floor; the tap conductors have no splices and are continuous from one end to the other and only qualified persons service the system.

(5) Outside Taps of Unlimited Length

(C) Transformer Secondary Conductors. There is a complete discussion of transformer taps. Among the items discussed are protection by primary overcurrent device, transformer secondary conductors not over 3 m (10 ft.) long, secondary conductors not over 7.5 m (25 ft.) long, outside secondary conductors, industrial installation secondary conductors not over 7.5 m (25 ft.) long, and secondary conductors from a feeder tapped transformer.

(D) Service Conductors

(E) Busway Taps. Busways and their taps can be protected in accordance with Sections 364.10 through 364.14.

(F) Motor Circuit Taps. Motor branch circuit conductors can be protected as indicated in Sections 430.28 and 430.53.

(G) Conductors from Generator Terminals. They can be protected as indicated in Section 445.4 if sized as per 445.5.

240.22

Grounded Conductors

No overcurrent device should be placed in series with a grounded conductor unless it simultaneously opens all other conductors of the circuit or when required by Sections 430.36 and 430.37.

240.23

Change in Size of Grounded Conductor

240.24

Location in or on Premises

Overcurrent devices must be readily accessible. The center of the grip of the handle on the overcurrent device has to be installed so that it is not more than 2.0 m (6 ft. 7 in.) above the floor or working platform at its highest position. There are four exceptions. Each occupant must have access to the ones protecting the conductors for his or her occupancy. The overcurrent devices must not be exposed to physical damage and must not be located near easily ignitible material or in bathrooms of dwelling units or guest rooms or guest suites of hotels and motels. Refer to the NEC® for certain exceptions.

III. Enclosures

240.30

General

240.32

Damp or Wet Locations

240.33

Vertical Position

IV. Disconnecting and Guarding

240.40

Disconnecting Means for Fuses

In general, the disconnection means must be provided on the supply side of the fuse. This does not hold true for service current-limiting devices as per Section 230.82 or single disconnecting devices for multiple sets of fuses as per Section 430.112 and Section 424.22(C).

240.41

Arcing or Suddenly Moving Parts

V. Plug Fuses, Fuseholders, and Adapters

These are not permitted in circuits where the voltage between conductors is more than 125 V except with a grounded neutral and not more than 150 V to ground. There are other requirements.

240.51

Edison-Base Fuses

240.52

Edison-Base Fuseholders

240.53

Type S Fuses

240.54

Type S Fuses, Adapters, and Fuseholders

VI. Cartridge Fuses and Fuseholders

These are permitted in circuits operating at 300 V between conductors if rated 300 V and for single-phase line to neutral circuits where this voltage is not larger than 300 V and the circuit is supplied from a three-phase, four-wire, solidly grounded neutral system. The holders must prevent interchangeability where a fuse can be put into a circuit of lower ampere rating or higher voltage rating. All fuses must be marked, indicating the current, voltage, and interrupting rating, if it is current limiting, and the manufacturer's name and trademark. The interrupting rating is not required when they are used for supplementary protection. Class H cartridge fuses that are renewable type can be used for replacement only in existing installations where there has been no overfusing or tampering.

VII. Circuit Breakers

240.80

Method of Operation

Normally, they must be trip free and capable of manual operation in addition to other normal means, such as electrical or pneumatic operation.

Must indicate on or offon is up position if mounted vertically.

They must all be properly marked. When properly used as a switch, they must be approved for switching duty and marked SWD or HID. There are requirements for voltage marking, interrupting ratings, and location.

240.85

Applications

240.86

Series Rating

VIII. Supervised Industrial Locations

240.90

General

240.92

Location in Circuit

IX. Overcurrent Protection over 600 Volts, Nominal

240.100

Feeders and Branch Circuits

240.101

Additional Requirements for Feeders

Page 4

I. General

Generally gives requirements for grounding and bonding.

250.2

Definitions

250.3

Application of Other Articles

The following other articles have special grounding requirements:

Table 250.3. Additional Grounding Requirements

Conductor/Equipment

Article

Section

Agricultural Buildings

 

547.9 and 547.10

Audio Signal Processing, Amplification, and Reproduction Equipment

 

640.7

Branch Circuits

 

210.5

   

210.6

   

406.3

Cablebus

 

370.9

Cable trays

392

392.3(C),

   

392.7

Capacitors

 

460.10

   

460.27

Circuits and Equipment Operating at Less Than 50 Volts

720

 

Class 1, Class 2, and Class 3
Circuits Remote Control, Signaling, and Power Limited Circuits

 

725.6

Closed-Loop and Programmed Power Distribution

 

780.3

Communications Circuits

800

 

Community Antenna Television and Radio Distribution Systems

 

820.33

   

820.40

   

820.41

Conductors for General Wiring

310

 

Cranes and Hoists

610

 

Electrically Driven or Controlled Irrigation Machines

 

675.11(C)

   

675.12

   

675.13

   

675.14

   

675.15

Electric Signs and Outline Lighting

600

 

Electrolytic Cells

668

 

Elevators, Dumbwaiters, Escalators, Moving Walks, Wheel Chair Lifts, and Stairway Chair Lifts

620

 

Fire Alarm Systems

 

760.6

Fixed Electric Heating Equipment for Pipelines and Vessels

 

427.29

   

427.48

Fixed Outdoor Electric Deicing and Snow-Melting Equipment

 

426.27

Flexible Cords and Cables

 

400.22

   

400.23

Floating Buildings

 

553.8

   

553.10

   

553.11

Grounding-Type Receptacles, Adapters, Cord Connectors, and Attachment Plugs

 

406.9

Hazardous (Classified) Locations

500517

 

Health Care Facilities

517

 

Induction and Dielectric Heating Equipment

665

 

Industrial Machinery

670

 

Information Technology Equipment

 

645.15

Intrinsically Safe Systems

 

504.50

Luminaires (lighting fixtures) and Lighting Equipment

 

410.17

   

410.18

   

410.20

   

410.21

   

410.105(B)

Luminaires (lighting fixtures), Lampholders, Lamps, and Receptacles

410

 

Marinas and Boatyards

 

555.15

Mobile Homes and Mobile Home Parks

550

 

Motion Picture and Television Studios and Similar Locations

 

530.20

   

530.66

Motors, Motor Circuits, and Controllers

430

 

Outlet, Device, Pull and Junction Boxes, Conduit Bodies, and Fittings

 

314.4

   

314.25

Over 600 Volts, Nominal, Underground Wiring Methods

 

350.50(B)

Panelboards

 

408.20

Pipe Organs

650

 

Radio and Television Equipment

810

 

Receptacles and Cord Connectors

 

406.3

Recreational Vehicles and Recreational Vehicle Parks

551

 

Services

230

 

Solar Photovoltaic Systems

 

690.41

   

690.42

   

690.43

   

690.45

   

690.47

Swimming Pools, Fountains, and Similar Installations

680

 

Switchboards and Panelboards

 

408.3(D)

Switches

 

404.12

Theaters, Audience Areas of Motion Picture and Television Studios, and Similar Locations

 

520.81

Transformers and Transformer Vaults

 

450.10

Use of Identification of Grounded Conductors

200

 

X-Ray Equipment

660

517.78

250.4

General Requirements for Grounding and Bonding

(A) Grounded Systems

(1) Electrical System Grounding. If the system is to be grounded, it has to be connected to earth so that it will limit voltages due to lightning, unintentional contact with higher voltages, and line surges. It must also stabilize line voltages during normal operation.

(2) Grounding of Electrical Equipment. Any non-current-carrying conductive material enclosing electrical conductors or equipment, or part of a piece of equipment must be connected to earth.

(3) Bonding of Electrical Equipment. All non-current carrying conductive material which encloses conductors or equipment must be connected together and to the electrical supply source.

(4) Bonding of Electrically Conductive Materials and Other Equipment. Any electrically conductive material that may become energized has to be bonded together and to the supply system at the source.

(5) Effective Ground Fault Current Path. The fault current path has to carry the maximum fault current, have low impedance and be continuous and permanent in nature.

The earth is not to be considered an effective ground-fault current path.

(B) Ungrounded Systems

(1) Grounding of Electrical Equipment. Non-current carrying conductive materials that enclose conductors or equipment must be connected to earth so that it will limit voltages due to lightning, unintentional contact and will limit the voltage to ground.

(2) Bonding of Electrical Equipment. All materials that enclose conductors or equipment must be connected together and to the supply system grounded equipment so that the fault current path carries maximum fault current, has low impedance and is continuous and permanent in nature. It must be capable of carrying the maximum fault current that can occur.

(3) Bonding of Electrically Conductive Materials and Other Equipment. Any electrically conductive material that can become energized has to be bonded together and to the supply system grounding equipment so that the fault current path carries maximum fault current, has low impedance, and is continuous and permanent in nature. It must be capable of carrying the maximum fault current that can occur.

(4) Path for Fault Current. The fault current path has to carry the maximum fault current path and have low impedance from any place on the system so that the overcurrent devices will operate on a second fault. The earth is not to be considered an effective fault current path.

There are two fine print notes.

250.6

Objectionable Current over Grounding Conductors

The entire electrical system is to be installed to prevent an objectionable flow of current over the grounding system. There is a discussion of alterations to stop objectionable current, limitations to permissible alterations, isolation of objectionable direct- current ground currents, and the fact that temporary currents are not classified as objectionable currents.

250.8

Connection of Grounding and Bonding Equipment

250.10

Protection of Ground Clamps and Fittings

250.12

Clean Surfaces

II. System Grounding

250.20

Alternating-Current Systems to Be Grounded

The following alternating-current systems must be grounded. Others may be grounded if desired.

(A) Alternating-current systems of less than 50 V must be grounded if supplied by transformer systems of more than 150 V to ground by ungrounded transformer systems and where the conductors are outdoors and overhead.

(B) Alternating-current circuits between 50 and 1000 V of the following types must be grounded:

  1. Systems of up to 150 V to ground from an ungrounded conductor
  2. Systems that are three-phase, four-wire with a neutral circuit conductor
  3. Three-phase, four-wire delta systems with the midpoint of one phase used as a circuit conductor

(C) Alternating-Current Systems 1 kV and Over

(D) Separately Derived Systems. If the source is separately derived, and covered in (A) or (B), it must be grounded as required by Section 250.30.

(E) Impedance Grounded Neutral Systems

250.21

Alternating Current Systems of 50 Volts to 1000 Volts Not Required to Be Grounded

There are a number of systems that are permitted to be grounded but are not required to be grounded. They are: electric systems used to supply industrial electric furnaces for melting, etc.; separately derived systems used only to supply rectifiers for adjustable speed industrial drives; other systems in accordance with 250.20(B) and separately derived systems supplied by transformers less than 1000 volts provided that special conditions are met. Where an alternating current system is not grounded as permitted above, ground detectors must be installed.

250.22

Circuits Not to Be Grounded

Those specified in Article 517, circuits for electric cranes used in areas of Class III over combustible fibers as indicated in Section 503.13, circuits for equipment in electrolytic cell working zones noted in Article 668 and lighting systems secondary circuits as noted in Section 411.5(A).

250.24

Grounding Service-Supplied Alternating-Current Systems

As required, each service must have a grounding electrode conductor connected to the grounded service conductor. The reader should be familiar with the requirements of this article in the NEC®. There is a discussion of system grounding connections in general and specifically from outdoor transformers, dual-fed services, using the main bonding jumper as wire or busbar, and loadside grounding connections. There is also a discussion of systems where the grounded conductor is brought to the service equipment, ungrounded system grounding connections, as well as the grounding electrode conductor.

250.26

Conductor to Be GroundedAlternating-Current Systems

One conductor must be grounded in a two-wire, single-phase system. The neutral conductor is grounded in a three-wire, single-phase system and a multiphase system where one phase is used as a three-wire, single-phase system. The common conductor is grounded in a multiphase system with one wire common to all phases. A phase conductor is grounded in a multiphase system where one phase is grounded and the neutral conductor is grounded in a multiphase system where one phase is used as a single phase 3 wire system.

250.28

Main Bonding Jumper and System Bonding Jumper

250.30

Grounding Separately Derived Alternating-Current Systems

250.32

Buildings or Structures Supplied by Feeder(s) or Branch Circuit(s)

Each building or structure must have a grounding electrode connected to the building grounding means. There are methods noted for grounded systems, ungrounded systems, where the disconnecting means is located in a separate building or structure on the same premises, and the size of the grounding electrode conductor. The size of grounding electrode conductor to the grounding electrode is given in 250.66 based on the largest ungrounded supply conductor. The reader should refer to this section in the NEC®.

250.34

Portable and Vehicle-Mounted Generators

250.36

High-Impedance Grounded Neutral Systems

III. Grounding Electrode System and Grounding Electrode Conductor

250.50

Grounding Electrode System

All grounding electrodes delineated in 250.52(A)(1) through (A)(6) have to be bonded together to form the grounding electrode system. If none exists, then at least one of the electrodes in 252(A)(4) through (A)(7) must be used.

250.52

Grounding Electrodes

(A) Electrodes Permitted for Grounding

(1) Metal Underground Water Pipe. It must be at least in contact with the earth for 3 m (10) or more feet. It must be electrically continuous to the point of connection to the grounding electrode system and bonding conductors. Interior water piping can not be used if it is more than 1.52 m (5 feet) from the point of entrance to the building. There is an exception for industrial and commercial buildings under certain conditions.

(2) Metal Frame of the Building or Structure. The metal frame of the building or structure can be used with any of the following methods:

(a) At least 3.0 m (10 ft.) of a structural member is in direct contact with the earth or it is encased in concrete that is in direct contact with the earth

(b) The structural metal frame is bonded to at least one grounding electrode as in 250.52(A)(1), (3), or (4)

(c) The structural metal frame is bonded to at least one or more grounding electrodes as noted in 250.52(A)(5) or (6) and complies with 250.56 or

(d) Any other approved method of establishing a connection to the earth.

(3) Concrete-Encased Electrode. The electrode must be at least 6 m (20 ft.) of 4 AWG bare copper conductor or 6 m (20 ft.) of steel or zinc galvanized reinforcing bars or rods at least 13 mm (½ in.) in diameter. It must be encased in at least 50 mm (2 in.) of concrete within or near the bottom of the foundation.

(4) Ground Ring

(5) Rod and Pipe Electrodes

(6) Plate Electrodes

(7) Other Local Metal Underground Systems or Structures

(B) Electrodes Not Permitted for Grounding. Metal underground gas piping and aluminum electrodes are not permitted. Refer to 250.104(B) for bonding requirements for gas piping.

250.53

Grounding Electrode System Installation

(A) Rod, Pipe, and Plate Electrodes

(B) Electrode Spacing

(C) Bonding Jumper

(D) Metal Underground Water Pipe

(E) Supplemental Electrode Bonding Site

(F) Ground Ring

(G) Rod and Pipe Electrodes

(H) Plate Electrode

250.54

Supplementary Grounding Electrodes

They are permitted to be connected to the equipment grounding conductors specified in Section 250.118. The earth can not be used as an effective ground-fault current path as noted in 250.4(A)(5) and 250.4(B)(4). They are not required to comply with bonding requirements of 250.50 or 250.53(C) or resistance requirements of 250.56.

250.56

Resistance of Rod, Pipe, and Plate Electrodes

250.58

Common Grounding Electrode

Where an ac system is grounded, the system and equipment must be grounded to the same electrode or electrodes bonded together.

250.60

Use of Air Terminal

You cannot use air terminals conductors and driven pipes, rods, or plate electrodes used for grounding air terminals in lieu of grounding electrodes as noted in Section 250.50. You can bond grounding electrodes of different systems.

250.62

Grounding Electrode Conductor Material

The material is to be solid or stranded copper, aluminum, or copper-clad aluminum. It can be bare, stranded, covered, or insulated. It must be corrosion resistant.

250.64

Grounding Electrode Conductor Installation

Install grounding electrode conductors as follows:

(A) Aluminum or Copper-Clad Aluminum Conductors. Where in direct contact with masonry or the earth where there are corrosive conditions, insulated or bare aluminum or copper-clad aluminum grounding conductors are not permitted. When used outside, these types of conductors cannot be used within 450 mm (18 in.) of the earth. The installation must be as noted below.

(B) Securing and Protection Against Physical Damage. If it is 4 AWG copper or aluminum or larger, it must be protected if it is subject to physical damage. 6 AWG wires, if fastened to the building and free from physical damage, do not need protection; if not, they must be protected in the same manner as wires smaller than 6 AWG. Wires smaller than 6 AWG must be enclosed in either rigid metal conduit, intermediate metal conduit, rigid nonmetallic conduit, electrical metallic tubing, or cable armor. In all cases above, the wire or enclosure must be fastened to the surface it is running on.

(C) Continuous. The grounding electrode conductors cannot have a splice or joint. A splice will be permitted only as noted below in (1) through (4).

(1) An irreversible compression-type fitting is used which is listed as grounding and bonding equipment or by an exothermic welding process.

(2) Sections of busbars can be connected together to form a grounding electrode conductor.

(3) Bonding jumpers from grounding electrodes and grounding electrode conductors can be connected to either an aluminum or copper busbar when the busbar is not less than 6 mm x 50 mm (¼ in. x 2 in.). Connections must be made by using a listed connector or the exothermic welding process. The busbar must be accessible and securely fastened.

(4) The installation must comply with 250.64(A) when aluminum busbars are used.

(D) Grounding Electrode Conductor Taps. Taps to the grounding electrode conductor are permitted where a service has more than one enclosure as noted in Section 230.40, Exception No. 2. The taps must go inside of the enclosure. The common grounding electrode conductor has to be sized in accordance with Section 250.66 based on the sum of the circular mil area of the largest ungrounded service entrance conductor. When, as permitted in 240.40 Exception No. 2, more than one set of service entrance conductors connect directly to a service drop or lateral, then the common grounding electrode conductor must be sized as per Table 250.66 Note 1. The tap conductors can be sized for the largest conductor. The tap conductor has to be connected to the grounding electrode conductor in such a way as to maintain the grounding electrode conductor without a splice.

Table 250.66. Grounding Electrode Conductor for Alternating-Current Systems

Size of Largest Ungrounded Service-Entrance Conductor or Equivalent Area for Parallel Conductors[1] (AWG/kcmil)

Size of Grounding Electrode Conductor (AWG/kcmil)

Copper

Aluminum or Copper-Clad Aluminum

Copper

Aluminum or Copper-Clad Aluminum[2]

2 or smaller

1/0 or smaller

8

6

1 or 1/0

2/0 or 3/0

6

4

2/0 or 3/0

4/0 or 250

4

2

Over 3/0 through 350

Over 250 through 500

2

1/0

Over 350 through 600

Over 500 through 900

1/0

3/0

Over 600 through 1100

Over 900 through 1750

2/0

4/0

Over 1100

Over 1750

3/0

250

Where multiple sets of service-entrance conductors are used as permitted in Section 230.40, Exception No. 2, the equivalent size of the largest service-entrance conductor shall be determined by the largest sum of the areas of the corresponding conductors of each set. Where there are no service-entrance conductors, the grounding electrode conductor size shall be determined by the equivalent size of the largest service-entrance conductor required for the load to be served.

[1] This table applies to the derived conductors of separately derived ac systems.

[2] See installation restrictions in Section 250.64(A).

(E) Enclosures for Grounding Electrode Conductors. A complete electrical path must be ensured for metal enclosures of grounding electrode conductors. If a raceway is used as protection for a grounding conductor, compliance is required with the appropriate article concerning the raceway.

(F) To Electrodes. A grounding conductor can be run to any convenient grounding electrode in the grounding electrode system or to one or more grounding electrodes or to aluminum or copper busbar as noted in 250.64(C). It must be sized for the largest grounding electrode required by the electrodes connected to it.

250.66

Size of Alternating-Current Grounding Electrode Conductor

These minimum sizes are given in Table 250.66. There are three special cases.

250.68

Grounding Electrode Conductor Connection to Grounding Electrodes

It must be accessible and provide an effective and permanent ground. There are two exeptions.

250.70

Methods of Grounding Conductor Connections to Electrodes

IV. Enclosure, Raceway, and Service Cable Grounding

250.80

Service Raceways and Enclosures

These metal enclosures and raceways must be grounded. There is an exception for a metal elbow installed in an underground installation under certain conditions.

250.84

Underground Service Cable or Raceway

(A) Underground Service Cable. A continuous underground armored or metal sheathed service cable bonded to the grounded underground system does not have to have the sheath or armor grounded at the building or structure. The armor or sheath can be insulated from the interior metal raceway conduit or piping.

(B) Underground Service Raceway Containing Cable. If an underground metal service raceway contains a metal sheathed or armored cable that is bonded to the grounded underground system, then it does not have to be grounded at the building or structure. The sheath or armor can be insulated from the interior metal raceway or piping.

250.86

Other Conductor Enclosures and Raceways

These metal enclosures and raceways must be grounded except as permitted in Section 250.112(I). Note three exceptions: for open wire, knob and tubing, and nonmetallic-sheathed cable; enclosures used to physically protect cable assemblies; and metal elbows under certain conditions.

V. Bonding

Bonding must be provided to make sure there is proper electrical continuity in the grounding system.

(A) Bonding at Services

All service equipment must be bonded, items are listed. A means must be provided for intersystem bonding.

(B) Method of Bonding at the Service

There are four approved methods:

(1) For the grounded service conductor use a method noted in Section 250.8

(2) Threaded couplings or threaded bosses made up wrench tight

(3) Threadless couplings and connectors for where made tight for metal raceways and metal-clad cables

(4) Other listed devices

250.94

Bonding for Other Systems

250.96

Bonding Other Enclosures

All items that will be used as grounding conductors must be bonded. There is a provision for isolated grounding circuits.

250.97

Bonding for over 250 Volts

250.98

Bonding Loosely Jointed Metal Raceways

250.100

Bonding in Hazardous (Classified) Locations

In a hazardous location as defined in Article 500, the electrical continuity of non-current carrying metal parts must be accomplished by using any of the methods described in 250.92(B)(2) through (4). This must be done even if supplementary equipment grounding conductors are used.

250.102

Equipment Bonding Jumpers

250.104

Bonding of Piping Systems and Exposed Structural Steel

250.106

Lightning Protection Systems

These ground terminals have to be bonded to the building ground system.

VI. Equipment Grounding and Equipment Grounding Conductors

250.110

Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed)

Metal parts of fixed equipment that are likely to become energized must be grounded if located in a wet or damp location and not isolated, if they can be touched by people and are 2.5 m (8 ft.) or less vertically and 1.5 m (5 ft.) or less horizontally to ground or a grounded object, if in contact with metal, if in a hazardous location, if metal-clad type of wiring is used under certain conditions, and if the voltage is greater than 150 V to ground. There are three exceptions.

250.112

Fastened in Place or Connected by Permanent Wiring Methods (Fixed)Specific

All exposed metal parts that do not conduct current of the following kinds of equipment and enclosures must be grounded: switchboard frames and structures except two-wire dc where insulated from ground: pipe organs; motor frames; enclosures for motor controllers; elevators and cranes; all electric equipment in commercial garages, theaters, and motion picture studios except pendant lampholders of 150 V or less: electric signs, outline lighting and associated equipment as noted in Article 600; motion picture equipment; power-limited remote-control, signaling, and fire-alarm signaling equipment supplied by Class 1, 2, and 3 circuits where required; luminaires (lighting fixtures) as per Article 410; skid-mounted equipment, motor-operated water pumps, and metal well casings.

250.114

Equipment Connected by Cord and Plug

There are areas where exposed metal parts (noncurrent-carrying) must be grounded even though connected by cord and plug. This is true of hazardous locations and circuits over 150 V to ground; two exceptions are motors when guarded and electrically heated appliances with special exemptions and insulation to ground. In a residence the following items are required to have equipment grounding: refrigerators, freezers, and air conditioners; clothes washing and clothes drying equipment, dishwashing machines, kitchen waste disposers, information technology equipment, sump pumps, and electrical aquarium equipment; hand-held motor-operated tools, stationary and fixed motor-operated tools, light industrial motor-operated tools; motor-operated hedge clippers, lawn mowers, snow blowers, wet scrubbers, etc.; and portable handlamps. In other than residences, the list is the same as residences, with the addition of cord- and plug-connected appliances in damp or wet locations and tools used in wet or conductive locations. There is an exception for tools and portable handlamps in wet or conductive locations if supplied through an isolating transformer with a secondary ungrounded and not over 50 V.

250.116

Nonelectric Equipment

The metal parts of this equipment must be grounded: cranes and hoists; elevator cars of nonelectric type; and electric elevators.

250.118

Types of Equipment Grounding Conductors

The following may be used for equipment grounding conductors.

  1. Copper or other corrosion-resistant conductor. It can be solid or stranded, and bare, covered, or insulated.
  2. Rigid metal conduit.
  3. Intermediate metal conduit.
  4. Electrical metallic tubing.
  5. Listed flexible metal conduit that meets the following requirements: the terminations are listed for grounding; the conductors in the conduit are protected by devices that are rated 20 A or less; and the total length of flexible metal conduit, flexible metallic tubing, and liquidtight flexible metal conduit in the same ground return path is not more than 1.8 m (6 ft.); if flexibility is required an equipment grounding conductor is used.
  6. Listed liquidtight flexible metal conduit meeting certain requirements.
  7. Flexible metal tubing under certain conditions.
  8. Armor of Type AC cable.
  9. The copper sheath of MI metal sheathed cable.
  10. Type MC cable under certain conditions.
  11. Cable trays as noted in Sections 318.3(c) and 318.7.
  12. Cablebus framework and noted in Section 365.2(A).
  13. Any other continuous metal raceways and auxiliary gutters that are continuous and listed for grounding.
  14. Listed surface metal raceways

250.119

Identification of Equipment Grounding Conductors

The equipment grounding conductor can either be bare, insulated, or covered unless there is a specific required by the code. There are identification requirements for conductors. Special requirements are listed for conductors larger than 6 AWG, multi-conductor cable, and flexible cord.

250.120

Equipment Grounding Conductor Installation

Where it is a raceway, cable tray, cable armor, cable bus, or cable sheath, or a wire in a raceway it must be installed in accordance with the NEC®. Aluminum and copper-clad aluminum can be used under certain circumstances. If the equipment grounding conductor is smaller than 6 AWG, it has to be protected from physical damage except under certain conditions where it is not subject to physical damage.

250.122

Size of Equipment Grounding Conductors

These minimum sizes are given in Table 250.122. When circuit conductors are run in parallel, the equipment grounding conductor must be run in parallel and sized according to the over-current device rating shown in the table. The conductor never has to be larger than the overcurrent device protecting the circuit conductor to the equipment. There are other requirements and exceptions, including where conductors are adjusted in size to compensate for voltage drop.

Table 250.122. Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment

Rating or Setting of Automatic Overcurrent Device in Circuit Ahead of Equipment, Conduit, etc., Not Exceeding (Amperes)

Size (AWG or kcmil)

Copper

Aluminum or Copper-Clad Aluminum[1]

15

14

12

20

12

10

30

10

8

40

10

8

60

10

8

100

8

6

200

6

4

300

4

2

400

3

1

500

2

1/0

600

1

2/0

800

1/0

3/0

1000

2/0

4/0

1200

3/0

250

1600

4/0

350

2000

250

400

2500

350

600

3000

400

600

4000

500

800

5000

700

1200

6000

800

1200

Note: Where necessary comply with 250.4(A)(5) or 250.4(B)(4), the equipment grounding conductor shall be sized larger than this table.

[1] See installation restrictions in Section 250.120.

250.124

Equipment Grounding Conductor Continuity

250.126

Identification of Wiring Device Terminals

VII. Methods of Equipment Grounding

250.130

Equipment Grounding Conductor Connections

250.132

Short Sections of Raceway

250.134

Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed)Grounding

250.136

Equipment Considered Effectively Grounded

(A) This is true when it is electrically connected to a supporting metal rack or structure that is properly grounded. The building's structural steel is not considered an effective grounding method.

(B) Metal car frames

250.138

Cord- and Plug-Connected Equipment

250.140

Frames for Ranges and Clothes Dryers

250.142

Use of Grounded Circuit Conductor for Grounding Equipment

(A) Generally, a grounded circuit conductor can be used to ground equipment on the supply side of the service disconnect, supply side of main disconnects for a separate building [Section 250.32(B)], and in a separate, derived system the supply side of the disconnecting or overcurrent devices.

(B) Generally, a grounded circuit conductor cannot be used to ground equipment on the load side of the service disconnect. There are four exceptions to this:

  1. As indicated in Section 250.140 for ranges, wall-mounted ovens, etc.
  2. Grounding meter enclosures if no service ground-fault protection is used, the meter is immediately adjacent to the service disconnecting means, and the grounded circuit conductor is not smaller than noted in Table 250.122 for equipment grounding conductors.
  3. Dc systems in accordance with Section 250.22, Exception.
  4. Ground electrode-type boilers over 600 V in accordance with 490.72(E)(1) and 490.74.

250.144

Multiple Circuit Connections

250.146

Connecting Receptacle Grounding Terminal to Box

Generally, an equipment bonding jumper must be used unless grounded as follows:

A. Surface Mounted Box. If the box is surface mounted and the yoke makes good electrical contact with the box or a contact yoke or device complying with 250.146(B). There are restrictions on cover-mounted receptacles.

B. Contact Devices or Yokes. Where the receptacle is listed as such with special yokes and screws.

C. Floor Boxes. Floor boxes so listed.

D. Isolated Receptacles. Where there is a requirement for the reduction of electrical noise, an insulated grounding conductor can be used. It is run with the circuit conductors. It can pass through panelboards without connection to the grounding terminal. The grounding terminal in the receptacle can be insulated from the mounting.

250.148

Continuity and Attachment of Equipment Grounding Conductors to Boxes

VIII. Direct Current Systems

250.162

Direct-Current Systems and Systems to Be Grounded

250.164

Point of Connection for Direct-Current Systems

250.166

Size of Direct-Current Grounding Electrode Conductor

It cannot be smaller than the neutral conductor for a three-wire balancer set or balancer winding. It cannot be smaller than the largest conductor if other than as stated in the preceding sentence. It can never be smaller than 8 AWG copper or 6 AWG aluminum. There are requirements for connections to make electrodes, concrete-encased electrodes, and ground rings.

250.168

Direct-Current Bonding Jumper

250.169

Underground Direct-Current Separately Derived Systems

IX. Instruments, Meters, and Relays

250.170

Instrument Transformer Circuits

250.172

Instrument Transformer Cases

250.174

Cases of Instruments, Meters, and Relays Operating at Less Than 1000 Volts

250.176

Cases of Instruments, Meters and Relays Operating at 1 kV and Over

250.178

Instrument Grounding Conductor

X. Grounding of Systems and Circuits of 1 kV and over (High Voltage)

If these systems are grounded, they must follow all previous sections as well as this section.

250.182

Derived Neutral Systems

250.184

Solidly Grounded Neutral Systems

250.186

Impedance Grounded Neutral Systems

250.188

Grounding of Systems Supplying Portable or Mobile Equipment

250.190

Grounding of Equipment

Page 5

I. General

280.1

Scope

280.2

Definition

280.3

Number Required

280.4

Surge-Arrester Selection

II. Installation

280.11

Location

280.12

Routing of Surge-Arrester Connections

III. Connecting Surge Arresters

280.21

Installed at Services of Less Than 1000 Volts

280.22

Installed on the Load Side of Services of Less Than 1000 Volts

280.23

Circuits of 1 kV and overSurge-Arrester Conductors

280.24

Circuits of 1 kV and overInterconnections

280.25

Grounding

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu

Page 6

I. General

285.1

Scope

285.2

Definition

285.3

Uses Not Permitted

285.4

Number Required

285.5

Listing

285.6

Short Circuit Current Rating

II. Installation

285.11

Location

280.12

Routing of Connections

III. Connecting Transient Voltage Surge Suppressors

285.21

Connection

280.25

Grounding

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu

Page 7

I. General Requirements

This article applies to all wiring installations except as noted in other articles. It does not apply to integral parts of equipment (e.g., motors, motor control centers, etc.) Metric designators and trade sizes for conduit, tubing, etc. are shown in Table 300.1(C).

Table 300.1(C). Metric Designator and Trade Sizes

Metric Designator

Trade Size

12

3/8

16

½

21

¾

27

1

35

41

53

2

63

78

3

91

103

4

129

5

155

6

Note: The metric designators and trade sizes are for identification purposes only and are not actual dimensions.

This chapter applies to voltages up to and including 600 V when not otherwise noted and over 600 V only when specifically mentioned in the National Electrical Code®.

(A) Single Conductors. The single conductors that are specified in Table 310.13 can be installed only as part of a recognized wiring method described in Chapter 3. Single overhead conductors are permitted if installed in accordance with 225.6.

(B) Conductors of the Same Circuit. All conductors of the same circuit including the grounded conductor and equipment grounding conductors must be installed in the same raceway, cable, etc. There are exceptions.

(C) Conductors of Different Systems

(1) 600 Volts, Nominal, or Less. Conductors of 600 V or less can occupy the same wiring enclosure if all conductors have insulation rated for the maximum voltage used. Refer to Section 690.4(B) for solar photovoltaic systems and to Section 725.55(A) for Class 2 and Class 3 conductors.

(2) Over 600 Volts, Nominal. Conductors of over 600 V cannot be in the same wiring enclosure with those rated 600 V or less except for secondary wiring to electric discharge lamps, primary leads of electric discharge lamp ballasts, and excitation, control, relay, ammeter conductors, motor switch gear and control assemblies, and in manholes under certain conditions.

Reference should be made to this section in the NEC® for a complete explanation.

300.4

Protection against Physical Damage

300.5

Underground Installations

(A) Minimum Cover Requirements. The cover requirements for direct buried cable or conduit are shown in Table 300.5. The reader should refer to it.

(B) Listing

(C) Underground Cables under Buildings

(D) Protection from Damage

(E) Splices and Taps

(F) Backfill

(G) Raceway Seals

(H) Bushing

(I) Conductors of the Same Circuit

(J) Ground Movement

(K) Directional Boring

300.6

Protection against Corrosion

Generally, all material used must be suitable for use in the installed environment.

(A) Ferrous Metal Equipment. Ferrous material must be protected both inside and out by a coating of corrosion-resistant material. If corrosion protection is required and threading takes place in the field, then the threads must be coated with an identified electrical conductive, corrosion-resistant compound. Stainless steel need not have a protective coating. If protected only by enamel ferrous metal equipment shall not be used outdoors or in wet locations as noted in 300.6(D). Boxes or cabinets with an approved organic coating and marked "Raintight," "Rainproof," or "Outdoor Type" can be used outdoors. If the material is approved for use in concrete, in direct contact with the earth, or subject to severe corrosion or has approved corrosion protection, then it can be used there.

(B) Non-Ferrous Metal Equipment. Non-ferrous material must have supplementary corrosion protection if embedded in or encased in concrete or in direct contact with the earth.

(C) Nonmetallic Equipment. Nonmetallic equipment must be made of material approved for the conditions in which it is installed. If exposed to sunlight then the material must be listed as sunlight resistant or be identified as sunlight resistant. If exposed to chemicals or their vapors, the material must be inherently resistant to the chemicals or identified for the specific chemical reagent.

(D) Indoor Wet Locations. The cable must be installed with at least 6 mm (¼ in.) of air space from the wall or supporting surface when installed exposed. There is an exception.

300.7

Raceways Exposed to Different Temperatures

300.8

Installations of Conductors with Other Systems

300.10

Electrical Continuity of Metal Raceways and Enclosures

There must be electrical continuity between all metal race-ways, cable armor, and metal enclosures. There are two exceptions.

300.11

Securing and Supporting

300.12

Mechanical ContinuityRaceways and Cables

300.13

Mechanical and Electrical ContinuityConductors

Splices or taps are not permitted within a raceway. Exceptions to this are noted in Sections 300.15; 368.8(A); 376.56; 378.56; 384.56; 386.56; 388.56; or 390.6. In a multiwire branch circuit the continuity cannot depend on device connections that can be removed.

300.14

Length of Free Conductors at Outlets, Junctions, and Switch Points

At least 150 mm (6 in.) of conductors must be left at every outlet, junction, or switch point for splices or connections. When the opening to the point of connection is less than 200 mm (8 in.), the conductors must extend at least 75 mm (3 in.).

300.15

Boxes, Conduit Bodies or FittingsWhere Required

For concealed knob and tube wiring a box must be installed at each switch point and outlet. Use fittings and connectors only for the purpose that they are listed and designed for. If the wiring method is conduit, tubing, Type AC cable, Type MC cable, Type MI cable, non-metallic sheathed cable or other cables, then a conduit body or box must be installed at each conductor splice point, switch point, outlet point, termination point, pull point and junction point. This requirement for the use of a conduit body or box is in force unless not required by (A) through (M) following.

(A) Wiring Methods With Interior Access. If the outlet method has a removable cover that is accessible after installation.

(B) Equipment. A wiring compartment or junction box that is part of approved equipment is allowed instead of a box.

(C) Protection. If the cables enter or leave conduit or tubing that is used for support or protection against physical damage. There are requirements for the use of fittings.

(D) Type MI Cable. If accessible fittings are used for straight through splices.

(E) Integral Enclosure. A wiring device with an integral enclosure that has brackets that fasten it to wall or ceilings for use with nonmetallic sheathed cable is permitted.

(F) Fitting. A fitting can be used instead of a conduit body or box as long as there are splices or terminations in the fitting. The fitting has to be accessible after the installation.

(G) Direct-Buried Conductors. As permitted in 300.5(E).

(H) Insulated Devices. As permitted in 334.40(B) where the insulated device is supplied by nonmetallic-sheathed cable.

(I) Enclosures. Where a splice, switch terminal, or pull point is in a cabinet or cut out box in an enclosure for a switch or overcurrent device as noted in 312.8 in a motor controller as noted in 430.10(A) or in a motor center.

(J) Luminaires (Fixtures). If the fixture is used as a raceway as permitted in 410.31 and 410.32.

(K) Embedded. Where conductors are embedded as permitted in 424.40, 424.41(D), 426.22(B), 426.24(A), and 427.19(A) they are not required for splices.

(L) Manholes and Handhole Enclosures. If only qualified persons have access in manholes except when connecting to electrical equipment and compliance with Part V of Article 110 for manholes and 314.30 for handhole enclosures.

(M) Closed Loop. If a device is identified and listed for installation without a box and is used with a closed loop power distribution system.

300.16

Raceway or Cable to Open or Concealed Wiring

300.17

Number and Size of Conductors in Raceway

In general, the number and size of conductors in a raceway must allow the dissipation of heat, easy installation, and withdrawal.

300.18

Raceway Installations

Raceways other than exposed raceways or busways that have hinged or removable covers must be installed complete between outlet, junction, or splicing points before the conductors are installed. Three exceptions are: (1) for prewired assemblies, (2) when necessary for the installation of utilization equipment, and (3) short sections used for protection from physical damage. There is a restriction on the use of welding.

300.19

Supporting Conductors in Vertical Raceways

Conductors must be supported at the top of vertical risers with additional support as noted in Table 300.19(A) of the NEC® when the rise is greater than the values in that table.

300.20

Induced Currents in Metal Enclosures or Metal Raceways

The effects of induced currents in metal enclosures must be minimized. This is done by grouping all phases, neutral, and grounding conductors in one raceway. If individual conductors are used, a slot can be cut between the holes made in the metallic enclosure through which the individual conductor passes. There are some exceptions.

300.21

Spread of Fire or Products of Combustion

300.22

Wiring in Ducts, Plenums, and Other Air-Handling Spaces

(A) Ducts for Dust, Loose Stock, or Vapor Removal. Wiring of any type is prohibited in these types of installations. This includes ventilation of commercial-type cooking equipment.

(B) Ducts or Plenums Used for Environmental Air. The following can be used when the duct or plenum was specifically made for this purpose: Type MI, Type MC cable with the specified sheath, EMT flexible metallic tubing, intermediate metal conduit, or rigid metal conduit. When necessary to connect physically adjustable items, flexible metal conduit can be used, but only in lengths not longer than 1.2 m (4 ft.). Only devices that act on or sense the contained air, such as thermostats, are permitted. If lighting fixtures are installed for maintenance or repair, they must be of the enclosed gasketed type. This paragraph applies primarily to fabricated ducts and plenums.

(C) Other Space Used for Environmental Air. This paragraph applies to spaces other than those in Sections 300.22(A) and (B) for environmental air handling. Habitable rooms or areas of buildings which are not primarily used for air handling are not included. Only totally enclosed nonventilated insulated busways that do not have a provision for plug-in connections and Type MI cable, Type MC cable without an overall nonmetallic covering, as well as Type AC cable or other factory-assembled multiconductor control or power cable made to be installed in these areas can be installed in this space. Other types of cables and conductors can be used but only when installed in EMT, flexible metallic tubing, intermediate metal conduit, rigid and flexible metal conduit, where accessible surface metal raceway or metal wireway with metal covers or solid bottom metal cable tray with solid metal covers. Also permitted is electric equipment with a metal enclosure or a listed nonmetallic enclosure with low smoke- and fire-resistive qualities suitable for the ambient temperature unless prohibited in another place in the Code.

(D) Information Technology Equipment. Refer to Article 645.

300.23

Panels Designed to Allow Access

II. Requirements for Over 600 Volts, Nominal

300.31

Covers Required

300.32

Conductors of Different Systems

See Section 300.3(C)(2).

300.34

Conductor Bending Radius

300.35

Protection against Induction Heating

300.37

Aboveground Wiring Methods

300.39

Braid-Covered Insulated Conductors-Exposed Installation

300.40

Insulation Shielding

300.42

Moisture or Mechanical Protection for Metal Sheathed Cables

300.50

Underground Installations

Page 8

Article 310 is to be used for general requirements for wiring, but not in areas where it is part of an integral device such as a motor, motor controller, or where covered in another part of the NEC®.

Conductors must be insulated and made of copper, copper-clad aluminum, or aluminum unless otherwise specified in the NEC®.

310.3

Stranded Conductors

Any conductor installed in a raceway must be stranded if it is 8 AWG or larger. This is not required if it is permitted or required in another part of the NEC®.

310.4

Conductors in Parallel

Conductors 1/0 AWG or larger and having each phase, polarity, neutral, or grounded circuit conductor can be run in parallel if they are the same length, the same size, and of the same material with the same insulation and terminated the same way. They must be electrically joined at both ends. The cables or raceways must have the same physical characteristics if the conductors are run in separate cables or raceways. The same numbers of conductors have to be used in each raceway or cable. The conductors of one phase, neutral, or ground do not have to have the same physical characteristics as those of another to achieve balance. There are four exceptions to this:

1. Section 620.12(A)(1), Exception.

2. If smaller than 1/0 AWG, used for control power to indicating instruments, relays, and similar devices, and in the same raceway, each individual conductor can carry the entire load and the overcurrent rating is not larger than the ampacity of any single conductor.

3. Sizes smaller than 1/0 AWG are allowed for frequencies of 360 Hz and higher provided that Exception 2 is met.

4. With engineering supervision 2 AWG or larger grounded neutral conductors can be run parallel in existing installations.

310.5

Minimum Size of Conductors

Minimum sizes are shown in Table 310.5 except as permitted in other sections of the Code®. For voltages up to 2000, it is 14 AWG for copper and 12 AWG for aluminum or copper-clad aluminum.

310.6

Shielding

310.7

Direct Burial Conductors

310.8

Locations

In dry locations any type of insulated conductor or cable noted in the Code can be used. Use only Type RHW, TW, THW, MTW, RHW-2, THW-2, THHW, THHW-2, THWN, THWN-2, XHHW, XHHW-2, ZW, or a type listed as such for a wet location, or a moisture impervious metal-sheathed conductor. For dry and damp locations use Types FEP, FEPB, MTW, PFA, RHW, RHH, RHW-2, SA, XHH, XHHW, XHHW-2, THHN, THW-2, THW, THHW, THHW-2, THWN, THWN-2, TW, Z, or ZW. If conductors are exposed to direct sunlight the cables must be listed as sunlight resistant; or conductors must be listed and identified as sunlight resistant; or insulated conductors can be covered with tape, sleeving, or similar material that is listed for the application and identified as sunlight resistant.

310.9

Corrosive Conditions

310.10

Temperature Limitations of Conductors

310.11

Marking

All conductors and cables must have marked on them the maximum rated voltage, the proper letter type, the manufacturer's name or trademark, the AWG size or circular mil area, and cable assemblies where the neutral conductor is smaller than the ungrounded conductor. The size markings should be on the surface and spaced not more than 610 mm (24 in.) for eight types of cables. Other markings may be spaced 1.0 m (40 in.) apart. Certain cables can use marker tape inside the cable. Refer to this section in the NEC® for specific types where marker tape is permitted, which cables can have the size located elsewhere, and suffix designations for number of conductors. Special characteristics can be surface-marked on conductors listed in Chapter 3.

310.12

Conductor Identification

(A) Grounded Conductors. Insulated grounded conductors must be identified as noted in Section 200.6.

(B) Equipment Grounding Conductors. Equipment grounding conductors must be as noted in Section 250.119.

(C) Ungrounded Conductors. These must be distinguished from grounded and grounding conductors.

310.13

Conductor Constructions and Applications

Insulated conductors must be in accordance with Tables 310.13 and 310.61 through 310.64.

310.14

Aluminum Conductor Material

310.15

Ampacities for Conductors Rated 0-2000 Volts

(A) General

(1) Tables or Engineering Supervision. Ampacities can be determined by tables as provided in (B) or under engineering supervision as noted in 310.15(C).

(2) Selection of Ampacity. If more than one ampacity is determined from the tables or calculations, the lowest value must be used. There is one exception for adjacent portions of a circuit under certain circumstances.

(B) Tables. Ampacities are noted in the Allowable Ampacities Tables 310.16 through 310.19 and 310.20 through 310.23 for conductors rated 0 to 2000 volts. They can be modified by paragraphs (1) through (6).

Table 310.16. Allowable Ampacities of Insulated Conductors, Rated 0 through 2000 Volts, 60° through 90°C (140° through 194°F) Not More than Three Current Conductors in Raceway, Cable, or Earth (Directly Buried) Based on Ambient Temperature of 30°C (86°F)

Size AWG or kcmil

Temperature Rating of Conductor (See Table 310.13)

Size AWG or kcmil

60°C (140°F)

75°C (167°F)

90°C (194°F)

60°C (140°F)

75°C (167°F)

90 °C (194°F)

Types TW, UF

Types RHW, THHW, THW, THWN, XHHW, USE, ZW

Types TBS, SA, SIS, FEP, FEPB, MI, RHH, RHW-2, THHN, THHW, THW-2, THWN-2 USE-2, XHH, XHHW, XHHW-2, ZW-2

Types TW, UF

Types RHW, THHW, THW, THWN, XHHW, USE,

Types TBS, SA, SIS, THHN, THHW, THW-2, THWN-2, RHH, RHW-2, USE-2, XHH, XHHW, XHHW-2, ZW-2

Copper

Aluminum or Copper-Clad Aluminum

18

. . . .

. . . .

14

. . . .

. . . .

. . . .

. . . .

16

. . . .

. . . .

18

. . . .

. . . .

. . . .

. . . .

14[*]

20

20

25

. . . .

. . . .

. . . .

. . . .

12[*]

25

25

30

20

20

25

12[*]

10[*]

30

35

40

25

30

35

10[*]

8

40

50

55

30

40

45

8

6

55

65

75

40

50

60

6

4

70

85

95

55

65

75

4

3

85

100

110

65

75

85

3

2

95

115

130

75

90

100

2

1

110

130

150

85

100

115

1

1/0

125

150

170

100

120

135

1/0

2/0

145

175

195

115

135

150

2/0

3/0

165

200

225

130

155

175

3/0

4/0

195

230

260

150

180

205

4/0

250

215

255

290

170

205

230

250

300

240

285

320

190

230

255

300

350

260

310

350

210

250

280

350

400

280

335

380

225

270

305

400

500

320

380

430

260

310

350

500

600

355

420

475

285

340

385

600

700

385

460

520

310

375

420

700

750

400

475

535

320

385

435

750

800

410

490

555

330

395

450

800

900

435

520

585

355

425

480

900

1000

455

545

615

375

445

500

1000

1250

495

590

665

405

485

545

1250

1500

520

625

705

435

520

585

1500

1750

545

650

735

455

545

615

1750

2000

560

665

750

470

560

630

2000

Correction Factors

Ambient Temp. °C

For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities shown above by the appropriate factor shown below.

Ambient Temp. °F

21-25

1.08

1.05

1.04

1.08

1.05

1.04

70-77

26-30

1.00

1.00

1.00

1.00

1.00

1.00

78-86

31-35

0.91

0.94

0.96

0.91

0.94

0.96

87-95

36-40

0.82

0.88

0.91

0.82

0.88

0.91

96-104

41-45

0.71

0.82

0.87

0.71

0.82

0.87

105-113

46-50

0.58

0.75

0.82

0.58

0.75

0.82

114-122

51-55

0.41

0.67

0.76

0.41

0.67

0.76

123-131

56-60

. . . .

0.58

0.71

. . . .

0.58

0.71

132-140

61-70

. . . .

0.33

0.58

. . . .

0.33

0.58

141-158

71-80

. . . .

. . . .

0.41

. . . .

. . . .

0.41

159-176

For table headings see page 94.

[*] See Section 240.4(D).

Table 310.20. Ampacities of Not More than Three Single-Insulated Conductors, Rated 0 through 2000 Volts, Supported on a Messenger, Based on Ambient Air Temperature of 40°C (104°F)

Size AWG or kcmil

Temperature Rating of Conductor (See Table 310.13)

Size AWG or kcmil

75°C (167°F)

90°C (194°F)

75°C (167°F)

90°C (194°F)

TYPES RHW, THHW, THW, THWN, XHHW, ZW

TYPES MI, THHN, THHW, THW-2, THWN-2, RHH, RWH-2, USE-2, XHHW, XHHW-2, ZW-2

TYPES RHW, THW, THWN, THHW, XHHW

TYPES THHN, THHW, RHH, XHHW, RHW-2, XHHW-2, THW-2, THWN-2 USE-2, ZW-2

Copper

Aluminum or Copper-Clad Aluminum

8

57

66

44

51

8

6

76

89

59

69

6

4

101

117

78

91

4

3

118

138

92

107

3

2

135

158

106

123

2

1

158

185

123

144

1

1/0

183

214

143

167

1/0

2/0

212

247

165

193

2/0

3/0

245

287

192

224

3/0

4/0

287

335

224

262

4/0

250

320

374

251

292

250

300

359

419

282

328

300

350

397

464

312

364

350

400

430

503

339

395

400

500

496

580

392

458

500

600

553

647

440

514

600

700

610

714

488

570

700

750

638

747

512

598

750

800

660

773

532

622

800

900

704

826

572

669

900

1000

748

879

612

716

1000

CORRECTION FACTORS

Ambient Temp. (°C)

For ambient temperatures other than 40° (104°F), multiply the ampacities shown above by the appropriate factor shown below.

Ambient Temp. (°F)

2125

1.20

1.14

1.20

1.14

7077

2630

1.13

1.10

1.13

1.10

7986

3135

1.07

1.05

1.07

1.05

8895

3640

1.00

1.00

1.00

1.00

97104

4145

0.93

0.95

0.93

0.95

106113

4650

0.85

0.89

0.85

0.89

115122

5155

0.76

0.84

0.76

0.84

124131

5660

0.65

0.77

0.65

0.77

133140

6170

0.38

0.63

0.38

0.63

142158

7180

0.45

0.45

160176

(1) General. For explanation of Type Letters, and for recognized size of conductors for the various conductor insulations, see Section 310.13. For installation requirements, see Sections 310.1 through 310.10, and the various articles of this Code. For flexible cords, see Tables 400.4, 400.5(A), and 400.5(B).

(2) Adjustment Factors

(a) More than Three Current-Carrying Conductors in a Raceway or Cable. Where the number of current-carrying conductors in a raceway or cable exceeds three, or where multi-conductor cables or single conductors are bundled or stacked longer than 600 mm (24 in.) without proper spacing and not in a raceway, the ampacities shall be reduced as shown in the following table Table 310.15(B)(2)(a). In a parallel set of conductors each conductor is counted as a current-carrying conductor. The exceptions to this are listed on the bottom of the table.

Table 310.15(B)(2)(a). Adjustment Factors for More than Three Current-Carrying Conductors in a Raceway or Cable

Number of Current-Carrying Conductors

Percent of Values in Tables Number of 310.16 through 310.19 Current-Carrying as Adjusted for Ambient Conductors Temperature if Necessary

4 through 6

80

7 through 9

70

10 through 20

50

21 through 30

45

31 through 40

40

41 and above

35

FPN Note 1: See Appendix B, Table B.310.11 for adjustment factors for more than three current-carrying conductors in a raceway or cable with load diversity.

FPN Note 2: For correction factors for conductors in sheet metal auxiliary gutters see 366.23(A) and 376.22 for conductors in metal raceways.

Exception No. 1. When conductors of different systems, as provided in Section 300.3, are installed in a common raceway or cable the derating factors shown in Table 310.15(B)(2)(a) shall apply to the number of power and lighting (Articles 210, 215, 220, and 230) conductors only.

Exception No. 2. For conductors installed in cable trays, the provisions of Section 392.11 shall apply.

Exception No. 3. Derating factors shall not apply to conductors in nipples having a length not exceeding 610 mm (24 in.).

Exception No. 4. Derating factors shall not apply to underground conductors entering or leaving an outdoor trench if those conductors have physical protection in the form of rigid metal conduit, intermediate metal conduit or rigid nonmetallic conduit having a length not exceeding 3 mm (10 ft.) and the number of conductors does not exceed 4.

Exception No. 5. Adjustment factors shall not apply to Type AC cable or to Type MC cable without an overall outer jacket under the following conditions:

(a) Each cable has not more than three current carrying conductors.

(b) The conductors are 12 AWG copper.

(c) Not more than 20 current carrying conductors are bundled, stacked, or supported on "bridle rings."

A 60 percent adjustment factor shall be applied where the current carrying conductors in these cables that are stacked or bundled longer than 600 mm (24 in.) without maintaining spacing exceeds 20.

(b) More than One Conduit, Tube, or Raceway. Spacing between conduits, tubing, or raceways shall be maintained.

(3) Bare Conductors or Covered Conductors

Where bare or covered conductors are used with insulated conductors, their allowable ampacities shall be limited to that permitted for the adjacent insulated conductors.

Table 310.21. Ampacities of Bare or Covered Conductors in Free Air, Based on 40°C (104°F) Ambient, 80°C (176°F) Total Conductor Temperature, 610 mm/sec (2 ft/sec) Wind Velocity

Copper Conductors

AAC Aluminum Conductors

Bare

Covered

Bare

Covered

AWG or kcmil

Amperes

AWG or kcmil

Amperes

AWG or kcmil

Amperes

AWG or kcmil

Amperes

8

98

8

103

8

76

8

80

6

124

6

130

6

96

6

101

4

155

4

163

4

121

4

127

2

209

2

219

2

163

2

171

1/0

282

1/0

297

1/0

220

1/0

231

2/0

329

2/0

344

2/0

255

2/0

268

3/0

382

3/0

401

3/0

297

3/0

312

4/0

444

4/0

466

4/0

346

4/0

364

250

494

250

519

266.8

403

266.8

423

300

556

300

584

336.4

468

336.4

492

500

773

500

812

397.5

522

397.5

548

750

1000

750

1050

477.0

588

477.0

617

1000

1193

1000

1253

556.5

650

556.5

682

636.0

709

636.0

744

795.0

819

795.0

860

954.0

920

1033.5

968

1033.5

1017

1272

1103

1272

1201

1590

1267

1590

1381

2000

1454

2000

1527

(4) Neutral Conductor

  1. A neutral conductor that carries only the unbalanced current from other conductors of the same circuit need not be counted when applying the provisions of Section 310.15(B)(2)(a).
  2. In a three-wire circuit consisting of two-phase wires and the neutral of a four-wire, three-phase wye-connected system, a common conductor carries approximately the same current as the line to neutral load currents of the other conductors and shall be counted when applying the provisions of Section 310.15(B)(2)(a).
  3. On a four-wire, three-phase wye circuit where the major portion of the load consists of nonlinear loads there are harmonic curents present in the neutral conductor and the neutral shall be considered to be a current-carrying conductor.

(5) Grounding or Bonding Conductor

A grounding or bonding conductor shall not be counted when applying the provisions of Section 310.15(B)(2)(a).

(6) 120/240 Volts, Three-Wire, Single-Phase Dwelling Services and Feeders

For individual dwelling units of one family, two-family, and multifamily dwellings, conductors, as listed in Table 310.15(B)(6), shall be permitted to be utilized as 120/240-V, three-wire, single-phase service-entrance conductors, service lateral conductors, and feeder conductors that serve as the main power feeder to a dwelling unit and are installed in raceway or cable with or without an equipment grounding conductor. For applications of this section, the main power feeder shall be the feeder(s) between the main disconnect and the lighting and appliance branch circuit panelboard(s). The feeder conductors to a dwelling unit shall not be required to be larger than its service-entrance conductors. The grounded conductor shall be permitted to be smaller than the ungrounded conductors, provided that the requirements of Sections 215.2, 220.61, and 230.42 are met.

Table 310.15(B)(6). Conductor Types and Sizesfor 120/240-Volt, Three-Wire, Single-Phase Dwelling Services and Feeders

Conductor (AWG or kcmil)

 

Copper

Aluminum or Copper-Clad Aluminum

Service or Feeder Ratings (Amperes)

4

2

100

3

1

110

2

1/0

125

1

2/0

150

1/0

3/0

175

2/0

4/0

200

3/0

250

225

4/0

300

250

250

350

300

350

500

350

400

600

400

(C) Engineering Supervision.

With engineering supervision the following formula can be used to calculate ampacities:

where

TC

= conductor temperature in degrees Celsius (°C)

TA

= ambient temperature in degrees Celsius (°C)

DELTA TD

= dielectric loss temperature rise

RDC

= dc resistance of conductor at temperature TC

YC

= component ac resistance resulting from skin effect and proximity effect

RCA

= effective thermal resistance between conductor and surrounding ambient

FPN: See Annex B for examples of formula application.

310.60

Conductors Rated 2001 to 35,000 Volts.

(A) Definitions.

(B) Ampacities of Conductors Rated 2001 to 35,000 Volts.

(C) Tables.

Page 9

I. Installation

312.2

Damp, Wet, or Hazardous (Classified) Locations

When installed in wet locations, they must be weatherproof. In damp or wet locations, surface boxes must prevent moisture from entering and have at least 6 mm (¼ in.) of air space between it and the wall or support. Raceways or cables entering above uninsulated live parts in enclosures in wet locations must use fittings listed for wet locations. Nonmetallic enclosures can be installed on concrete, tile, or masonry without an airspace. In hazardous locations conformance must be made with the requirements of Articles 500 through 517.

When installed in noncombustible material, they may be set back 6 mm (¼ in.) When installed in combustible material, they must be flush with the surface.

312.4

Repairing Plaster and Drywall or Plasterboard

If a plaster, drywall, or plasterboard surface is broken or incomplete it must be repaired so that there are no open spaces or gaps larger than 3 mm (¼ in.) at the edge of the cabinet or cutout box that employs a flush-type cover.

312.5

Cabinets, Cutout Boxes, and Meter Socket Enclosures

The opening must be closed. When metal cabinets, boxes, or enclosures are used with open wiring or knob-and-tube work, the conductors must come in through an insulated bushing. In dry areas, they may enter through flexible tubing. Cables must be secured to the box. There is an exception.

312.6

Deflection of Conductors

Refer to Tables 312.6(A) through (C) in the NEC® for minimum width of gutters and bending spaces.

312.7

Space in Enclosures

312.8

Enclosures for Switches or Overcurrent Devices

312.9

Side or Back Wiring Spaces or Gutters

II. Construction Specifications

If metal, it must have corrosion protection. Sheet steel cabinets must be at least 1.35 mm (0.053 in.) thick uncoated. Nonmetallic cabinets must be approved by the authorities.

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu

Page 10

I. Scope and General

Refer to this section in the NEC® for inclusions and exclusions.

These are not permitted if locknuts or bushings are required on the side of the box.

These are only to be used with nonmetallic sheathed cable or raceways, flexible cords, open wire on insulator installations, or knob-and-tube concealed wiring. They can be used with metal raceway or metal-jacketed cable only if there is a means for integral bonding or internal bonding. There are two exceptions.

These must be grounded.

314.5

Short Radius Conduit Bodies

Conduit bodies, like capped elbows, which enclose 6 AWG or smaller conductors and are used only to allow the installation of the raceway and its conductors can not have splices, taps, or devices and they must be large enough for free space for the conductors.

II. Installation

314.15

Damp, Wet Locations or Hazardous (Classified) Locations

Moisture must be prevented from getting into the box. They must be listed for use in wet locations. When installed in a hazardous location, conform to Articles 500 through 517.

314.16

Number of Conductors in Outlet, Device and Junction Boxes, and Conduit Bodies

The reader is referred to this section for complete information. These items must be large enough to allow free space for all the enclosed conductors. The volume of the box as calculated in this section cannot be smaller than the fill calculation. This does not apply to terminal housings supplied with the motors (refer to Section 430.12). For enclosed conductors 4 AWG or larger, the provisions of Section 314.28 must be complied with.

(A) Box Volume Calculations. The volume is the total of the assembled sections and if used, spaces from plaster rings, domed covers, extension rings, and the like that are made from boxes listed in Table 314.16(A) or have the volume marked.

Table 314.16(A). Metal Boxes

Box Trade Size

Minimum Volume

Maximum Number of Conductors[*]

mm

in.

 

cm3

in.3

18

16

14

12

10

8

6

100 x 32

(4 x 1¼)

round/octagonal

205

12.5

8

7

6

5

5

5

2

100 x 38

(4 x 1½)

round/octagonal

254

15.5

10

8

7

6

6

5

3

100 x 54

(4 x 21/8)

round/octagonal

353

21.5

14

12

10

9

8

7

4

100 x 32

(4 x 1¼)

square

395

18.0

12

10

9

8

7

6

3

100 x 38

(4 x 1½)

square

344

21.0

14

12

10

9

8

7

4

100 x 54

(4 x 21/8)

square

497

30.3

20

17

15

13

12

10

6

120 x 32

(4

x ¼)

square

418

25.5

17

14

12

11

10

8

5

120 x 38

(4

x 1½)

square

484

29.5

19

16

14

13

11

9

5

120 x 54

(4

x 21/8)

square

689

42.0

28

24

21

18

16

14

8

75 x 50 x 38

(3 x 2 x 1½)

device

123

7.5

5

4

3

3

3

2

1

75 x 50 x 50

(3 x 2 x 2)

device

164

10.0

6

5

5

4

4

3

2

75 x 50 x 57

(3 x 2 x 2¼)

device

172

10.5

7

6

5

4

4

3

2

75 x 50 x 65

(3 x 2 x 2½)

device

205

12.5

8

7

6

5

5

4

2

75 x 50 x 70

(3 x 2 x 2¾)

device

230

14.0

9

8

7

6

5

4

2

75 x 50 x 90

(3 x 2 x 3½)

device

295

18.0

12

10

9

8

7

6

3

100 x 54 x 38

(4 x 21/8 x 1½)

device

169

10.3

6

5

5

4

4

3

2

100 x 54 x 48

(4 x 21/8 x 17/8)

device

213

13.0

8

7

6

5

5

4

2

100 x 54 x 54

(4 x 21/8 x 21/8)

device

238

14.5

9

8

7

6

5

4

2

95 x 50 x 65

(3¾ x 2 x 2½)

masonrybox/gang

230

14.0

9

8

7

6

5

4

2

95 x 50 x 90

(3¾ x 2 x 3½)

masonry box/gang

344

21.0

14

12

10

9

8

7

2

min. 44.5 depth

FSsingle cover/gang (1¾)

221

13.5

9

7

6

6

5

4

2

min. 60.3 depth

FDsingle cover/gang (23/8)

295

18.0

12

10

9

8

7

6

3

min. 44.5 depth

FSmultiple cover/gang (1¾)

295

18.0

12

10

9

8

7

6

3

min. 60.3 depth

FDmultiple cover/gang (23/8)

395

24.0

16

13

12

10

9

8

4

[*] Where no volume allowances are required by 314.16(B)(2) through 314.16(B)(5).

(1) Standard Boxes. Given in Table 314.16(A).

(2) Other Boxes. If the box is 100 cubic inches or less [except those in Table 314.16(A)] and nonmetallic boxes must have the capacity marked by the manufacturer. If the box is listed in Table 314.16(A) and has a larger capacity, the manufacturer can mark it.

(B) Box Fill Calculations.

(1) Conductor Fill. Every conductor that originates outside the box and terminates or is spliced in the box and each conductor passing through the box is counted once. A conductor that is looped and unbroken which is not less than twice the minimum length for a free conductor as referred to in 300.14 is counted twice. The fill is computed using Table 314.16(B). If a conductor has no part leaving the box, it is not counted. There is an exception for equipment grounding conductors.

(2) Clamp Fill. If an internal clamp is used there, a single volume allowance in accordance with Table 314.16(B) is made based on the largest conductor in the box.

(3) Support Fittings Fill. If a stud or hickey is there, a single volume allowance in accordance with Table 314.16(B) is made based on the largest conductor in the box.

(4) Device or Equipment Fill. For a strap or yoke containing a device or equipment, a double volume allowance is made in accordance with Table 314.16(B) based on the largest conductor connected to the device or equipment.

(5) Equipment Grounding Fill. If equipment grounding conductors come into the box, a single volume allowance is made in accordance with Table 314.16(B) and is based on the largest equipment grounding conductor present. If additional equipment grounding conductors as noted in 250.146(D), come into the box an additional volume allowance is made based on the largest equipment grounding conductor in this set.

Table 314.16(B). Volume Allowance Required per Conductor

 

Free Space within Box for Each Conductor

Size of Conductor (AWG)

cm3

m3

18

24.6

1.50

16

28.7

1.75

14

32.8

2.00

12

36.9

2.25

10

41.0

2.50

8

49.2

3.00

6

81.9

5.00

(c) Conduit Bodies. Generally conduit bodies enclosing 6 AWG conductors or smaller must have cross-sectional area not less than twice the area of the largest conduit or tubing attached. The maximum number of conductors is shown in Table 1, Chapter 9. There are additional requirements noted in the Code.

314.17

Conductors Entering Boxes, Conduit Bodies, or Fittings

All openings must be closed. All conductors coming into a box, conduit body, or fitting must be protected against abrasion. Special requirements are indicated with open wiring or concealed knob-and-tube wiring. If cable or raceway is used, the cable or raceway must be fastened to the box, conduit body, or fitting. Refer to Section 300.15(C) of the NEC® for an exception and to Section 300.4(F) for wire 4 AWG or larger. The reader is referred to this section for complete details.

314.19

Boxes Enclosing Flush Devices

They must be closed on the back and sides and a support for the device (usually a stud or screw hole) must be in the box. The screw that supports the box cannot be used to attach the device.

314.20

In Wall or Ceiling

When the box is set in concrete, tile, or other noncombustible material, it can be set back as much as 6 mm (¼ in.) When it is set in combustible material, it has to be flush with the finished surface.

314.21

Repairing Plaster and Drywall or Plasterboard

314.22

Exposed Surface Extensions

314.23

Supports

This section details methods of support. It indicates where they are needed and what can be used.

314.24

Depth of Outlet Boxes

314.25

Covers and Canopies

314.27

Outlet Boxes

They must be designed for the purpose to be used (i.e., floor or lighting fixture). A fixture support must be in a lighting fixture box. Cannot be used as sole support for ceiling paddle fans unless listed for that purpose. There are special cases. The reader is referred to this section in the NEC®.

314.28

Pull and Junction Boxes and Conduit Bodies

(A) Minimum Size. The following rules apply only when the wire is 4 AWG or larger. In a straight pull, the box must be at least 8 times the metric/designator (trade size) of the largest raceway in length. When angle pulls or U-pulls are used, the distance between the raceway entrances and the opposite wall must be at least 6 times the metric designator (trade size) of the largest raceway in a row. In addition, that distance must be increased by the diameter of each additional raceway in any one row on the same wall of the box. Since each row is calculated individually, the largest distance for a single row is used. Two raceways that enclose the same conductor cannot be closer than 6 times the metric designator (trade size) of the larger raceway. There is an exception where the entry is opposite a removable cover. There is also a provision for boxes or conduit bodies whose dimensions are less than calculated where combination of conductors are used.

(B) Conductors in Pull or Junction Boxes

(C) Covers

(D) Permanent Barriers. If a permanent barrier is in a box, each section is considered a box.

314.29

Boxes and Conduit Bodies to Be Accessible

314.30

Handhole Enclosures

They must be designed and installed to withstand any load that might be imposed.

(A) Size. For conductors operating at 600 volts or lower, they must be sized as stated in 314.28(A). For conductors operating above 600 volts they must be sized as stated in 314.71. There is a provision for handholes without bottoms.

(B) Wiring Entries. If underground raceways and cable assemblies enter a handhole they must extend into the enclosure but are not required to be mechanically connected to the enclosure.

(C) Handhole Enclosures Without Bottoms. All enclosed conductors, splices, or terminations must be listed for wet locations if installed in a handhole without a bottom.

(D) Covers. They have to have an identifying mark or logo that tells the function of the handhole. The example given in the Code is "electric." They must weigh over 45 kg (100 lb.) or require the use of tools to open. Any metal cover and any exposed conductive surface has to be bonded in accordance with 250.96(A).

III. Construction Specifications

314.40

Metal Boxes, Conduit Bodies, and Fittings

314.41

Covers

314.42

Bushings

314.43

Nonmetallic Boxes

314.44

Marking

IV. Pull and Junction Boxes for Use on Systems Over 600 Volts, Nominal

314.70

General

314.71

Size of Pull and Junction Boxes

314.72

Construction and Installation Requirements

Page 11

I. General

320.1

Scope

320.2

Definition

This type of cable is composed of insulated conductors in a flexible metal enclosure. Refer to 320.100.

II. Installation

It can be used exposed or concealed and in cable trays where so identified. It is permitted in dry locations and in plaster finish on brick or other masonry except in damp or wet locations. It can also be used in the voids of masonry block or tile walls when the walls are not exposed or subject to excessive moisture or dampness. There is a fine print note that this is not an all-inclusive list.

320.12

Uses Not Permitted

It cannot be used if subject to physical damage, in damp or wet locations, embedded in plaster finish on brick or any other masonry in damp or wet locations, in air voids of masonry block or tile when the walls are exposed to excessive dampness or moisture, or where it is exposed to corrosive vapors or fumes.

320.15

Exposed Work

320.17

Through or Parallel to Framing Members

320.23

In Accessible Attics

320.24

Bending Radius

They must be made so that the cable will not be damaged and the radius of the curve of the inner edge cannot be less than five times the diameter of the cable.

320.30

Securing and Supporting

320.40

Boxes and Fittings

320.80

Ampacity

III. Construction Specifications

The cable consists of insulated conductors enclosed in a flexible metal tape armor with a copper or aluminum bonding strip inside and in contact with the armor.

320.104

Conductors

320.108

Grounding

320.120

Marking

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu

Page 12

I. General

322.1

Scope

322.2

Definition

II. Installation

322.10

Uses Permitted

322.12

Uses not Permitted

322.30

Securing and Supporting

322.40

Boxes and Fittings

322.56

Splices and Taps

III. Construction

322.100

Construction

322.104

Conductors

322.112

Insulation

322.120

Marking

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu

Page 13

I. General

The wiring covered in this article is a field-installed system to be used for branch circuits under carpet squares.

The reader is referred to the Code for these definitions.

324.6

Listing Requirements

II. Installation

It can be used for general-purpose, appliance, and individual branch circuits; on floors that are hard, sound, or smooth made of materials like or similar to concrete, ceramic, composition, and wood; on walls in surface metal raceways; in damp locations; and on heated floors where the temperature is higher than 86°F if approved for those temperatures.

The voltage ratings are up to 150 V to ground and up to 300 V between ungrounded conductors. The current ratings are up to 20 A for general-purpose and appliance branch circuits and up to 30 A for individual branch circuits.

When on a floor, it must be covered with carpet squares. Release-type adhesive only is permitted. If it exceeds 2.3 mm (0.09 in.) above floor level it must be feathered or tapered at the edges to floor level. There are other requirements for corrosion resistance and metal-shield connectors.

324.12

Uses Not Permitted

It cannot be used outdoors, in wet locations, in classified hazardous locations, where there are corrosive vapors present, or in residential, school, or hospital buildings.

324.18

Crossings

324.30

Securing and Supporting

324.40

Boxes and Fittings

324.41

Floor Coverings

324.42

Devices

324.56

Splices and Taps

324.60

Grounding

III. Construction

324.100

Construction

324.101

Corrosion Resistance

324.112

Insulation

324.180

Markings

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu

Page 14

I. General

326.1

Scope

326.2

Definition

II. Installation

326.10

Uses Permitted

326.12

Uses Not Permitted

326.24

Bending Radius

326.26

Bends

326.40

Fittings

326.80

Ampacity

III. Construction Specifications

326.104

Conductors

326.112

Insulation

326.116

Conduit

326.120

Marking

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu

Page 15

I. General

328.1

Scope

328.2

Definition

This cable is rated above 2000 V and is a single or multiconductor solid dielectric insulated cable.

II. Installation

It can be used in dry or wet locations, in raceways, directly buried in accordance with 300.50, in messenger supported wiring, and in cable trays in accordance with 392(B)(2).

328.12

Uses Not Permitted

It cannot be used in cable trays unless specified in 392.3(B)(2); nor can it be exposed to direct sunlight or buried unless as specified in 300.50 and unless it is identified for that purpose.

III. Construction Specifications

328.100

Construction

328.120

Marking

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu

Page 16

I. General

330.1

Scope

330.2

Definition

Metal-clad cable is Type MC. It is a cable in which the conductors are enclosed in a corrugated metal sheath or interlocking metal tape, insulated, and the entire cable is put together at the factory.

II. Installation

This cable can be used for almost all types of applications, including wet locations, provided that it will not sustain physical damage and is not prohibited in another part of the NEC®. A listing is given in the NEC® for both general uses and specific uses. In wet locations one of the following must be adhered to: moisture will not get through the metal cover, a lead sheath that will not let moisture through is put under the metal cover, or the insulated conductors enclosed by the metal cover are listed for a wet location. Refer to this section in the Code.

Type MC cable must be installed in accordance with the requirements of Articles 300, 490, 725, and Section 770.133. When installed in cable tray, direct buried, as service-entrance cable outside buildings or as aerial cable, you must refer to the appropriate articles in the NEC®.

330.12

Uses Not Permitted

This cable cannot be used in a location where it is subject to corrosive conditions that are destructive. The NEC® gives as examples direct buried cable in earth or concrete, under fills, chlorides, caustic alkalis, and the like.

330.17

Through or Parallel to Framing Members

It must comply with 300.4.

330.23

In Accessible Attics

Must comply with 320.23.

The following are the allowable radii of the curve of the inner edge: for shielded conductors, use the greater of either 12 times the diameter of one conductor or 7 times the overall diameter of the cable; for interlocked armor or corrugated sheath, 7 times the diameter of the sheath; for smooth sheath, use the following:

Cable up to 19 mm (¾ in.) diameter: 10 times diameter

Cable between 19 mm (¾) and 38 mm (1½ in.) diameter: 12 times diameter

Cable larger than 38 mm (1½ in.) diameter: 15 times diameter

330.30

Securing and Supporting

There are requirements for supported and unsupported cables.

330.31

Single Conductors

330.40

Boxes and Fittings

330.80

Ampacity

Refer to 310.15 or 310.60 for 14 AWG and larger conductors. Use Table 402.5 for 18-16 AWG conductors. There are additional requirements for cable installed in cable tray and cable grouped together supported by messenger cable.

C. Construction Specifications

Copper, aluminum, or copper-clad aluminum must be used, either stranded or solid. The smallest sizes allowed are 18 AWG for copper and 12 AWG for aluminum or copper-clad aluminum.

330.108

Equipment Grounding

330.112

Insulation

The sheath must be either smooth, welded, and corrugated or interlocking.

Page 17

I. General

332.1

Scope

332.2

Definition

Type MI cable is factory assembled with one or more conductors using a highly compressed refractory mineral insulation. The entire assembly is covered with a gastight and liquidtight continuous copper or alloy steel sheath.

II. Installation

It can be used for services, feeders, and branch circuits; power, control, lighting, and signal circuits; wet, dry, or continuously moist locations; exposed or concealed; indoors and outdoors; embedded in concrete, plaster, fill, and other masonry; hazardous locations; underground when protected; corrosive locations that will not harm the sheath; where exposed to gasoline and oil, in or attached to cable trays and in underground runs when protected against corrosion or physical damage.

332.12

Uses Not Permitted

Where exposed to corrosive materials that will harm the sheath unless it is properly protected and in underground runs unless it is protected against physical damage.

332.17

Through or Parallel to Framing Members

332.24

Bending Radius

332.30

Securing and Supporting

332.31

Single Conductors

332.40

Boxes and Fittings

332.80

Ampacity

III. Construction Specifications

Solid copper, nickel, or nickel-coated copper.

332.108

Equipment Grouding

332.112

Insulation

Highly compressed refractory mineral.

Continuous construction that ensures mechanical protection and a moisture seal.

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu

Page 18

I. General

334.1

Scope

334.2

Definition

Nonmetallic-sheathed cable is a cable in which the insulated conductors are enclosed in a nonmetallic material that is moisture-resistant and flame-retardant. The cable is put together at the factory. There are definitions for NM, NMC, and NMS.

II. Installation

These types of cable can be used in one- and two-family dwellings, multifamily dwellings of types III, IV, and V construction except as noted in Section 334.12, and cable trays when they are noted for this use. These cables can also be used in other structures of Types III, IV, and V construction with limitations. Type NM cable can be used both in dry locations exposed and concealed as well as being fished in air voids of block and tile if it is not damp or moist. Type NMC cable can be used exposed or concealed in damp, dry, or corrosive locations, inside and outside of block walls, and in shallow chases protected against nails or screws. Type NMS can be used in the same locations as Type NM. The reader is referred to this section of the NEC® for a complete list of locations where these cables can be used.

334.12

Uses Not Permitted

Type NM, NMC, and NMS cannot be used in any dwelling not permitted in 334.10(1), (2), and (3); as service entrance cable; exposed in suspended or dropped ceilings in other than one family, two family, and multifamily dwellings; in commercial garages; in motion picture studios; in theatres and the like unless otherwise provided in the NEC®; in hoistways or on elevators or escalators; in storage battery rooms; in hazardous locations unless otherwise provided in the NEC®; and embedded in poured cement, concrete, or aggregate. There are additional limitations for Types NM and NMS cable. The reader is referred to this section of the NEC® for a complete list of locations where types NM, NMC, and NMS are not permitted.

334.15

Exposed Work

334.17

Through or Parallel to Framing Members

334.23

In Accessible Attics

334.24

Bending Radius

334.30

Securing and Supporting

The cable must be secured at least every 1.4 m (4½ ft.) and not more than 300 mm (12 in.) from a fitting, box, or cabinet. There are requirements for cable trays, unsupported cable, and wiring devices without a separate outlet box.

334.40

Boxes and Fittings

334.80

Ampacity

III. Construction Specifications

334.100

Construction

334.104

Conductors

334.108

Equipment Grounding

334.112

Insulation

334.116

Sheath

Page 19

I. General

336.1

Scope

336.2

Definition

This cable is factory assembled with a nonmetallic jacket containing two or more insulated conductors with or without bare or covered grounding conductors.

II. Installation

This cable can be used for power, lighting, control, and signal circuits; in cable trays, raceways, or supported by messenger wire; under certain conditions where permitted by Article 725 for Class 1 circuits; for nonpower-limited fire alarm circuits in accordance with Section 760.27; and for industrial establishments with qualified supervision and maintenance. There are additional requirements for support, identification, and equipment grounding in industrial locations. If installed in wet locations the cable must be resistant to moisture and corrosive agents.

336.12

Uses Not Permitted

Type TC cable cannot be used where exposed to physical damage; installed outside of a cable tray system or raceway unless permitted in 336.10(6); where exposed to direct sunlight unless sunlight resistant; and direct buried unless approved for that purpose.

336.24

Bending Radius

336.80

Ampacity

III. Construction Specifications

A metallic sheath cannot be put over or under the nonmetallic sheath. Metallic sheaths can be put over groups of conductors, under the outer jacket or both.

Minimum-size conductors are 18 AWG for copper and 12 AWG for aluminum and copper-clad aluminum. Maximum size is 1000 kcmil. 14 AWG copper and larger and 12 AWG or larger aluminum or copper-clad aluminum are to be of the types shown in Table 310.13 or 310.62.

(A) Fire Alarm Systems. It must be installed as noted in Section 760.27 for fire alarms systems.

(B) Thermocouple Circuits. It must be installed as noted in Article 725, Part III. There are additional requirements.

(C) Class 1 Circuit Conductors. When insulated conductors of sizes 18 AWG or 16 AWG copper are used, they shall be as noted in Section 725.27.

The outer jacket must be a flame-retardant, nonmetallic material.

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu

Page 20

I. General

338.1

Scope

338.2

Definition

This cable is either Type SE or USE and is used primarily for services. Type SE has a flame-retardant and moisture-resistant cover. Type USE, which is the one used underground, has a moisture-resistant cover.

II. Installation

(A) Service-Entrance Conductors. When used as service- entrance conductors, you must follow 230.6, 230.7, and Parts II, III, and IV of Article 230. If protected as noted in Section 300.5(D), Type USE can come above ground outside in meter enclosures or terminations when used as a service lateral.

(B) Branch Circuits or Feeders.

(1) Grounded Conductor Insulated. Type SE can be used if all conductors are rubber-covered or thermoplastic type.

(2) Grounded Conductor Not Insulated. Generally, Type SE cable can be used where the insulated conductor is used for circuit wiring in a building and where the uninsulated conductor is used only for equipment grounding. There is an exception.

(3) Temperature Limitations. Do not exceed temperature specified.

(4) Installation Methods for Branch Circuits and Feeders.

Review applicable sections of the NEC®.

III. Construction

338.100

Construction

338.120

Marking

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu

Page 21

I. General

340.1

Scope

340.2

Definition

A factory assembly with an integral covering of nonmetallic material for direct burial in the earth.

340.6

Listing Requirements

II. Installation

It can be used for underground work including direct burial. Refer to 300.5 for underground requirements. If used as single conductor cables, all conductors of the feeder grounded conductor or branch circuit, including the grounded conductor and equipment grounding conductor, must conform to 300.3. It can be used for interior wiring in wet, dry, or corrosive areas provided that all other conditions are met. In certain of these cases, as described in Section 690.31, it can be used for solar photovoltaic systems. Single conductor cables can be nonheating leads for heating cable. If supported by cable trays, this cable must be multiconductor. If installed in accordance with Parts II and III of Article 334 it can be used as nonmetallic sheathed cable. In this case it must be multiconductor type.

340.12

Uses Not Permitted

This type of cable cannot be used for service entrances, in commercial garages, in theaters, in storage battery rooms, in motion picture studios, in hazardous locations, in hoistways, in poured cement except as permitted in 424.43, where exposed to direct rays of sun unless approved for sunlight installation, where subject to physical damage, or as an overhead cable except as messanger supported wiring.

340.24

Bending Radius

340.80

Ampacity

Refer to 310.15, 60°C (140°F) conductors.

III. Construction Specifications

This cable is Type UF. Sizes allowed are minimum 14 AWG copper or 12 AWG aluminum or copper-clad aluminum and maximum 4/0 AWG.

340.108

Equipment Grounding

The cable can have an insulated or bare conductor only for equipment grounding purposes.

Moisture resistant type found in Table 310.13. If installed as a substitute for NM cable, the insulation must be rated at 90°C (194°F).

Flame retardant; moisture, fugus, and corrosion resistant, suitable for direct burial in earth.

Page 22

I. General

342.1

Scope

342.2

Definition

This conduit is a circular metal raceway threadable and designed for the protection and routing of conductors and cable. It can be used as an equipment grounding conductor with its couplings and fittings.

342.6

Listing Requirements

IMC, the factory elbows, couplings, and fittings must be listed.

II. Installation

Intermediate metal conduit can be used in most places and under most conditions. It can be used in the earth or in corrosive locations if it has corrosion protection. It can be used in cinder fill only if 50 mm (2 in.) of noncinder concrete is in direct contact, the conduit is 450 mm (18 in.) or more under the fill, or there is proper corrosion protection. In wet locations all supports, belts, screws, etc. must be protected against corrosion.

With the exception of aluminum fittings and enclosures, dissimilar metals in contact must not be used where possible.

The conduit used cannot be smaller than metric designator 16 (trade size ½) or larger than metric designator 103 (trade size 4). See 300.1(C) for metric designators.

342.22

Number of Conductors

Refer to Chapter 9, Table 1. Cables can be used if not prohibited by cable articles. Cable cannot exceed fill requirements of Table 1, Chapter 9.

The conduit must not be injured. Refer to Table 2, Chapter 9, for the radius of the curve for field bends.

342.26

BendsNumber in One Run

The maximum that is permitted is not more than 360° in bends between pull points.

342.28

Reaming and Threading

All rough edges must be removed when the conduit is cut. When threaded in the field, a tapered cutting die with a taper of 1 in 16 (¾ in. taper per foot) must be used.

342.30

Securing and Supporting

It must be installed as a complete system and fastened and supported as noted in (A) and (B) below.

(A) Securely Fastened. It must be securely fastened within 900 mm (3 ft.) of all boxes, cabinets, conduits, or other conduit terminations. When structural members interfere with this, then the distance can be increased to 1.5 m (5 ft.). If approved, it does not have to be fastened within 900 mm (3 ft.) of a service head above a roof.

(B) Supports. It has to be supported at intervals no longer than 3 m (10 ft.). Table 344.30(B)(2) indicates the spacing of supports for straight runs of conduit with the proper couplings and there is a prevention of the transmission of stresses. Exposed vertical risers can be supported at intervals of 6 m (20 ft.), if the couplings are threaded, firmly supported at top and bottom, and there is no other intermediate support available. Horizontal runs that are supported by framing members not longer than 3 m (10 ft.) apart with supports within 900 mm (3 ft.) of the terminations are permitted.

342.42

Couplings and Connectors

Threadless couplings and connectors can be used and should be made tight. Comply with 314.15(A). Running threads cannot be used. Use concrete type in concrete and in wet areas. Do not use threadless couplings and connectors on threaded conduit unless it is listed for that use.

A bushing must be used at the point where the conduit goes into a box, fitting, or other enclosure. This is to protect the wire. An exception is made if protection is provided with the box or fitting.

They are permitted only if made in accordance with Section 300.15.

III. Construction Specifications

The conduit must be marked every 1.5 m (5 ft.) with the letter IMC and as required by 110.24.

This type of conduit has a standard length of 3 m (10 ft.) with one coupling and both ends threaded. Shorter or longer lengths with or without couplings or threads are permitted.

Page 23

I. General

344.1

Scope

344.2

Definition

Rigid metal conduit is a raceway that is listed, has a cross section that is circular, has integral or associated couplings, is used with listed fittings to give electrical continuity, and is approved for the installation of electrical conductors.

344.6

Listing Requirements

This type of conduit, associated fittings, factory elbows and couplings must be listed.

II. Installation

(A) All Atmospheric Conditions and Occupancies. It is permitted in all atmospheric conditions and all occupancies. If the conduit's protection against corrosion is only enamel, it can be used only indoors and in areas that do not have severe corrosive problems. Aluminum enclosures and fittings can be used with steel conduit and vice versa.

(B) Corrosion Environments. If the conduit is protected from corrosion and is suitable, the conduit, elbows, couplings, and fittings can be installed in concrete, in areas where there is a severe corrosive problem, and in direct contact with the earth.

(C) Cinder Fill. It cannot be used in or under cinder fill when there may be permanent moisture unless it is suitable for this type of installation, there are 50 mm (2 in.) or more of noncinder concrete all around it, it is at least 450 mm (18 in.) under the fill, or where it is suitable for the condition and has corrosion protection.

(D) Wet Locations. Everything must be corrosion-resistant (bolts, straps, etc.).

Contact between dissimilar metals must be avoided where possible to eliminate galvanic action. Aluminum fittings are permitted with steel and vice versa where not subject to severe corrosion.

Metric designator 16 (trade size ½) is the minimum size permitted unless used for enclosing motor leads [see Section 430.145(B)]. The maximum size permitted is metric designator 155 (trade size 6). See 300.1(C) for metric designators.

344.22

Number of Conductors in Conduit

Refer to Chapter 9, Table 1. Cables can be used if not prohibited by cable articles. Cable cannot exceed fill requirements of Table 1, Chapter 9.

The conduit must not be damaged and the internal diameter will not be reduced. Refer to Table 2, Chapter 9, for the radius to the center line of the conduit for field bends.

344.26

BendsNumber in One Run

The maximum that is permitted is not more than 360° in bends between pull points.

344.28

Reaming and Threading

All rough edges must be removed when the conduit is cut. When threaded in the field, a tapered cutting die 1 in 16 taper (¾ in. taper per foot) must be used.

344.30

Securing and Supporting

The conduit must be supported at intervals no longer than 3 m (10 ft.) and fastened not more than 900 mm (3 ft.) from a box, fitting, etc. It must be installed as a complete system in accordance with 300.18. Fastening can be increased to 1.5 m (5 ft.) where structural members do not permit fastening within 900 mm (3 ft.). For supports for straight runs with threaded couplings, refer to Table 344.30(B)(2). No stress is to be transmitted to the terminations. Vertical risers from industrial machinery or fixed equipment can have the distance between supports at 6 m (20 ft.) if the conduit uses threaded couplings and is properly supported at the top and bottom. Where approved, the conduit does not have to be fastened within 900 mm (3 ft.) of a service head for a termination of a mast above the roof. Horizontal runs that are supported by openings through framing members not less than 3 m (10 ft.) and fastened within 900 mm (3 ft.) of termination points are permitted.

344.42

Couplings and Connectors

Threadless couplings and connectors can be used and made tight. Running threads cannot be used. Use concrete type in masonry or concrete. Comply with 314.15(A) in wet locations. Do not use threadless couplings and connectors on threaded conduit unless it is listed for that use.

A bushing must be used at the point where the conduit goes into a box, fitting, or other enclosure. This is to protect the wire. An exception is made if protection is provided with the box or fitting.

Refer to Article 300.15.

It is permitted as an equipment grounding conductor.

III. Construction Specifications

If the conduit is nonferrous of corrosion-resistant material, it must be marked to indicate it. At every 3 m (10 ft.) the conduit must be marked with identification (refer to Section 110.21).

This type of conduit has a standard in length of 3 m (10 ft.) including one attached coupling. It has to be threaded at each end. Smaller and larger lengths can be used with or without couplings and threads.

Page 24

I. General

348.1

Scope

348.2

Definition

This is a circular raceway of helically wound, formed, interlocked metal strip.

348.6

Listing Requirements

Must be listed.

II. Installation

It can be used in exposed and concealed locations.

348.12

Uses Not Permitted

It cannot be used in wet locations unless approved for this and the liquid does not get into the conduit, in hoistways unless permitted by Section 620.21(A)(1), in storage battery rooms, in hazardous locations unless allowed by Sections 501.4(B) and 504.20, where materials might deteriorate conductors, underground or in poured concrete or aggregate, and where subject to physical damage.

Minimum size permitted is metric designator 12 (trade size 3/8). The use of metric designator 12 (3/8) is allowed for leads to motors [Section 430.145(b)], not longer than 1.8 m (6 ft.) as part of a listed assembly or taps to lighting fixtures [Section 410.67(C)] or utilization equipment, for manufactured wiring systems [Section 604.6(A)], in hoistways Section 620.21, and as permitted by Section 410.77(C) as part of a listed assembly to connect wired fixture sections. There are five exceptions. The maximum size permitted is metric designator 103 (trade size 4).

348.22

Number of Conductors

Cannot exceed the percentage fill of Table 1, Chapter 9. Cables can be used if not prohibited by cable articles. Cable cannot exceed the fill requirements of Table 1, Chapter 9.

Bends must not damage the conduit and must not reduce the internal diameter of the conduit. Bends can be made with auxiliary equipment manually. The radius of the curve to the centerline can not be less than that shown in Table 1, Chapter 9. Use the "Other Bends" column.

348.26

BendsNumber in One Run

The maximum number that is permitted is not more than 360 degrees in bends between pull points. The radius of curve of the inner edge of a field bend must comply with Table 346.10.

348.28

Trimming

348.30

Securing and Supporting

Securely fasten within 300 mm (12 in.) of a termination point and supports must be not more than 1.4 m (4½ ft.) apart. There is a provision for supports through framing openings. There are four exceptions.

348.42

Couplings and Connectors

348.56

Splices and Taps

They can be made only in accordance with 300.15.

348.60

Grounding and Bonding

An equipment grounding conductor must be installed when the conduit is used to connect equipment where flexibility is needed. It can be used as an equipment grounding conductor where flexibility is not required in accordance with 250.48(5) or (6). The equipment grounding conductor must be installed in accordance with 250.134(B). Equipment bonding conductors must be installed in accordance with 250.102.

Page 25

I. General

350.1

Scope

350.2

Definition

This conduit is similar to flexible metal conduit, but it has a jacket over the metal conduit. The jacket is liquidtight, nonmetallic, and sunlight-resistant.

350.6

Listing Requirements

II. Installation

This conduit can be installed exposed or concealed, directly buried in earth and if protection from liquids, vapor, or solids is necessary or if flexibility is desired. It can be installed in hazardous areas if approved for that installation. Refer to Sections 501.4(B), 502.4, 503.3, 504.20, and 553.7(B).

350.12

Uses Not Permitted

It cannot be installed when subject to damage or where temperatures exceed that which is approved for the material.

Minimum metric designator 16 (trade size ½). For exceptions, refer to Section 348.20(A). The maximum size allowed is metric designator 103 (trade size 4). Refer to 300.1(C) for metric designators and trade sizes.

350.22

Number of Conductors or Cables

(A) Metric Designators 16 through 103 (Trade Sizes ½ through 4). Refer to Table 1, Chapter 9. Cables can be used if not prohibited by cable articles. Cables cannot exceed the fill requirements of Table 1, Chapter 9.

(B) Metric Designator 12 (Trade Size 3/8). Refer to the Fittings Outside Conduit columns in Table 348.22.

Bends must not damage the conduit and must not reduce the internal diameter of the conduit. Bends can be made with auxiliary equipment manually. The radius of the curve to the centerline can not be less than that shown in Table 2, Chapter 9. Use the "Other Bends" column.

350.26

BendsNumber in One Run

The maximum that is permitted is not more than 360° in bends between pull points.

350.30

Securing and Supporting

It must be supported and secured not more than 1.4 m (4½ ft.) apart. It must be securely fastened within 300 mm (12 in.) of a conduit termination. Four exceptions are for when the conduit is fished, where flexibility is needed, length not exceeding 900 mm (3 ft.) at terminals, lengths not exceeding 1.8 m (6 ft.) from a fixture terminal connection for tap conductors to a lighting fixture as noted in Section 410.67(C) and within accessible ceilings for lengths not exceeding 1.8 m (6 ft.) from the last point where the raceway is fastened, for connections to luminaires or other equipment. Horizontal runs allowed to be supported by the openings in framing members not more than 1.4 m (4½ ft.) apart and fastened within 300 mm (12 in.) of a termination.

350.42

Couplings and Connectors

350.56

Splices and Taps

They can be made only in accordance with Section 300.15.

350.60

Grounding and Bonding

This type of conduit can be used as a means of grounding under certain conditions. Refer to the NEC®.

III. Construction Specifications

Page 26

I. General

352.1

Scope

352.2

Definition

A conduit which is circular in cross section and made from a nonmetallic material.

352.6

Listing Requirements

The RNC, elbows, and associated fittings must be listed.

II. Installation

Some of the uses permitted and other references in the NEC® are: concealed in walls, floors, ceilings, and cinder fill; exposed when not subject to injury; in corrosive locations where approved for that type of location and in accordance with Section 300.6; in dry and damp locations in accordance with Section 352.12; in wet locations where the entire system is installed to prevent water from getting into the conduit and all bolts, screws, and so forth are corrosion resistant and underground in accordance with Sections 300.5 and 300.50. There is a provision for use as a support in certain specific cases.

352.12

Uses Not Permitted

This type of conduit must not be used in hazardous locations except where permitted by Sections 503.10(A), 504.20, 514.8 exception 2, 515.8, and the Class 1, Division 2 locations in Section 501.10(B)(3); in areas where there might be physical damage to the conduit; in theaters and similar locations except as noted in Articles 518 and 520; where the temperature rating of the conduit is exceeded by that of the conductor insulation; in areas where the ambient temperature exceeds 50°C (122°F) unless otherwise listed; and for supporting fixtures or other equipment not described in 352.10(H).

The minimum size is metric designator 16 (trade size ½). The maximum size is metric designator 155 (trade size 6).

352.22

Number of Conductors

Cannot exceed the percentage fill of Table 1, Chapter 9. Cables can be used if not prohibited by cable articles. Cable cannot exceed the fill requirements of Table 1, Chapter 9.

The conduit must not be injured. Refer to Table 2, Chapter 9.

352.26

BendsNumber in One Run

The maximum that is permitted is not more than 360° in bends between pull points.

Remove rough edges on cuts.

352.30

Securing and Supporting

Refer to Section 300.18 and Table 352.30(B) for spacing of supports. It must be fastened no farther than 900 mm (3 ft.) from a termination point. If it is listed for other securing spacing, it is permitted to follow but not exceed the listing. There is an exception for supports by openings through framing members of horizontal runs.

352.44

Expansion Fittings

Expansion fittings have to be provided to compensate for thermal expansion and contraction where the change in length according to Table 352.44(A) or (B) will be 6 mm (¼ in.) or greater between securely mounted conduit terminations.

Table 352.44(A). Expansion Characteristics of PVC Rigid Nonmetallic Conduit Coefficient of Thermal Expansion = 6.084 x 105 mm/mm/°C (3.38 x 105 in./in./°F)

Temperature Change (°C)

Length Change of PVC Conduit (mm/m)

Temperature Change (°F)

Length Change of PVC Conduit (in./100 ft.)

Temperature Change (°F)

Length Change of PVC Conduit (in./100 ft.)

5

0.30

5

0.20

105

4.26

10

0.61

10

0.41

110

4.46

15

0.91

15

0.61

115

4.66

20

1.22

20

0.81

120

4.87

25

1.52

25

1.01

125

5.07

30

1.83

30

1.22

130

5.27

35

2.13

35

1.42

135

5.48

40

2.43

40

1.62

140

5.68

45

2.74

45

1.83

145

5.88

50

3.04

50

2.03

150

6.08

55

3.35

55

2.23

155

6.29

60

3.65

60

2.43

160

6.49

65

3.95

65

2.64

165

6.69

70

4.26

70

2.84

170

6.90

75

4.56

75

3.04

175

7.10

80

4.87

80

3.24

180

7.30

85

5.17

85

3.45

185

7.50

90

5.48

90

3.65

190

7.71

95

5.78

95

3.85

195

7.91

100

6.08

100

4.06

200

8.11

Table 352.44(B). Expansion Characteristics of Reinforced Thermosetting Resin Conduit (RTRC) Coefficient of Thermal Expansion = 2.7 x 105 mm/mm/°C (1.5 x 105 in./in./°F)

Temperature Change (°C)

Length Change of PVC Conduit (mm/m)

Temperature Change (°F)

Length Change of PVC Conduit (in./100 ft.)

Temperature Change (°F)

Length Change of PVC Conduit (in./100 ft.)

5

0.14

5

0.09

105

1.89

10

0.27

10

0.18

110

1.98

15

0.41

15

0.27

115

2.07

20

0.54

20

0.36

120

2.16

25

0.68

25

0.45

125

2.25

30

0.81

30

0.54

130

2.34

35

0.95

35

0.63

135

2.43

40

1.08

40

0.72

140

2.52

45

1.22

45

0.81

145

2.61

50

1.35

50

0.90

150

2.70

55

1.49

55

0.99

155

2.79

60

1.62

60

1.08

160

2.88

65

1.76

65

1.17

165

2.97

70

1.89

70

1.26

170

3.06

75

2.03

75

1.35

175

3.15

80

2.16

80

1.44

180

3.24

85

2.30

85

1.53

185

3.33

90

2.43

90

1.62

190

3.42

95

2.57

95

1.71

195

3.51

100

2.70

100

1.80

200

3.60

A bushing must be used at the point where the conduit goes into a box or fitting unless protection is provided in the box or fitting.

Use approved methods.

They are permitted only in accordance with Section 300.15.

A separate equipment grounding conductor must be installed where equipment grounding is required. There are two exceptions.

III. Construction Specifications

RNC and fittings must be composed of a nonmetallic material. It must be resistant to moisture and chemical atmospheres. Above ground it must be flame resistant, resistant to impact and crushing, resistant to distortion from heat, and resistant to low temperature and sunlight. Below ground it must be resistant to corrosive agents and moisture, be able to withstand crushing and other abuse. If it is direct buried without encasement in concrete, it must be able to resist the continued loading it will encounter.

It must be marked at least every 3 m (10 ft.) in each length. There are requirements for marking on conduit used above and below ground.

Última postagem

Tag